6.10. Power Quality - Option
Place the curser on
“10. POWER QUALITY”
in
SYSTEM SETUP
menu, press [ENT] button to
move into this menu. Power Quality elements are set in this menu and sub-menu is as below.
SYSTEM SETUP / POWER QUALITY / S-O Func (Option)
Range
Disable, Enable
Default
Disable
Step
~
It is to set event recording of supply outage enable or disable.
Outage time, number of times and duration can be viewed in menu,
“MAINTENANCE” and “EVENT RECORDER.”
Refer to
“11.4. Power Quality – Option”
for more information.
SYSTEM SETUP / POWER QUALITY / S-O Duration (Option)
Range
1 ~3600 sec
Default
20
Step
1 sec
It is to set event recording detect supply outage and to set time to get
recovered from supply outage.
Refer to
“11.4. Power Quality – Option”
for more information.
SYSTEM SETUP / POWER QUALITY / SAG Func (Option)
Range
Disable, Enable
Default
Disable
Step
~
It is to set event recording of sag enable or disable.
SYSTEM SETUP / POWER QUALITY / SAG Pickup (Option)
Range
0.30 ~ 0.95
×
VT(secondary nominal voltage)
Default
0.80
Step
0.01
Set a detect level of Voltage sag(low voltage) for Power Quality.
Detect level is set by multiplying a set value in here to source side rated
voltage.
>
[POWER QUALITY]
>
S-O Duration: 20
>
SAG Func: Disable
>SAG Pickup: 0.80
>
[POWER QUALITY]
>
S-O Func: Disable
>
S-O Duration: 20
>SAG Func: Disable
>
[POWER QUALITY]
>
S-O Func: Disable
>S-O Duration: 20
>
SAG Func: Disable
[POWER QUALITY]
>S-O Func: Disable
>
S-O Duration: 20
>
SAG Func: Disable