RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
214
EN
HANCED
TEC
HNOLOGY
3)
Limit value Setting
Setting for Trip Counter Monitor value.
PRIMARY SETTING / MONITORING / TRIP COUNTER / Limit
Range
1 ~ 20000
Default
10000
Step
1
Select for system to operate when Trip Counter limit value was picked
up.
4)
Clear value Setting
Use to synchronize EVRC2A counter with Recloser Counter.
PRIMARY SETTING / MONITORING / TRIP COUNTER / Counter set
Range
0 ~ 10000
Default
0
Step
1
Enters a value for Trip Counter Clear.
5)
Stored Value Clear
Select
“7.Counter”
in
“PRIMARY SETTING / RELAY SETUP / CLEAR SAVED DATA”
to clear the Trip Counter.
[TRIP COUNTER]
Relays(0-8): OFF
Limit: 10000
>Counter set: 0
[TRIP COUNTER]
Function: OFF
Relays(0-8): OFF
>Limit: 10000