RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
248
EN
HANCED
TEC
HNOLOGY
12.3.4. Related Setting Menu
1)
ON/OFF Setting
Load Profile can be set ON/OFF by user.
PRIMARY SETTING / RELAY SETUP / EVENT RECORDER / Load Profile
Range
OFF, ON
Default
ON
Step
~
ON :
Records load profile.
OFF :
No record of load profile.
2)
Recording time interval setting
PRIMARY SETTING / RELAY SETUP / EVENT RECORDER / L.P save time(m)
Range
5, 10, 15, 20, 30, 60 min
Default
15
Step
~
Sets the interval time between Records.
12.3.5. Stored value Clear
Select
“3. LOAD PROFILE”
in
“PRIMARY SETTING / RELAY SETUP / CLEAR SAVED
DATA”
to clear.
[EVENT RECORDER]
Len' of Pre F: 4
Load Profile: ON
>L.P save time(m):15
[EVENT RECORDER]
Fault Cycle: ON
Len' of Pre F: 4
>Load Profile: ON