RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
94
EN
HANCED
TEC
HNOLOGY
6.7.2. Setting
PRIMARY SETTING / SYSTEM SETUP / OUTPUT RELAY SET / O1 Func
Range
NONE, TRIP, … , NEQ FLT
*
Default
NONE
Step
~
Enter the function of External output terminal.
Output Relay can have following function.
NONE TRIP CLOSE
FAIL TRIP
FAIL CLOSE
FAIL AC
FAIL BATTTERY
27 ELEMENT
59 ELEMENT
25 ELEMENT
81 ELEMENT
79 RESET
79CYCLE 79LOCKOUT
SELFCHECK
PROTECTION Enable
GROUND Enable
SEF Enable
RECLOSE Enable
CONTROL Locked
REMOTE Enable
ALTERNATE SETTINGS
Enable
PROGRAM1 Enable
PROGRAM2 Enable
HOT LINE TAG Enable
LO/RE OPEN
ALARM
CLOSE - 52A
INPUT 1~ 8
GAS LOW*
OPEN - 52B*
SYSTEM OK*
CLOSE BLOCK*
MECHANISM LOCK*
GAS LOW LOCK*
EXT’ TRIP LOCK*
INST FAULT*
DELAY FAULT*
HIGH CURRENT
LOCKOUT FAULT*
PHASE FAULT*
GROUND FAULT*
SEF FAULT*
NEQ FAULT*
For more detail, refer to
“Appendix B. RELAY OUTPUT
FUNCTION”
.
NOTE :
The function marked with ‘*’ is an option. That function
may not be supported by the option type.
PRIMARY SETTING / SYSTEM SETUP / OUTPUT RELAY SET / O1 Type
Range
PULSE, LATCH, S/R LATCH
Default
S/R LATCH
Step
~
S/R LATCH:
Output signal is delivered only this function activates (ON).
PULSE:
Output signal is delivered only during PULSE T. To activate
Output again, turn this function OFF and then, turn it ON again.
LATCH:
Output signal is delivered once this function ON. To turn it
off, it needs Reset signal and it is set in “OPTO INPUT SET”
[OUTPUT RELAY SET]
O1 Func: NONE
>O1 Type: S/R LATCH
O1 Pulse T: 0.05
[OUTPUT RELAY SET]
>O1 Func: NONE
O1 Type: S/R LATCH
O1 Pulse T: 0.05