Page 3: ...ATION 8 4 1 Wall Fixation 9 4 1 1 I Pillar Fixation 9 4 1 2 Sandwich Fixation 9 4 2 Control Box Installation 10 5 ELECTRICAL INSTALLATION 11 5 1 Box Control 12 5 2 Modbus control optional 12 5 2 1 Multiple Fan Installation 13 5 2 2 Recommendations 14 6 OPERATION 15 7 BASIC OPERATIONS 16 7 1 Operating panel 16 7 2 The data display 16 8 FAULT DIAGNOSIS 17 9 MAINTENANCE 18 ...

Page 4: ... fire or other accidents Ensure that the wires are held securely and protected from abrasion chaffing overload or other damage Risk of serious or fatal electrical shock fire or other accidents Turn Off power to the fan if you detect any damage Risk of serious or fatal electrical shock fire or other accidents Do NOT connect a damaged fan to the power supply Risk of serious or fatal electrical shock...

Page 5: ...as pivoting function up to 34º The AIRPIVOT fan can be controlled directly from a keyboard located in a control box or through general control via Modbus The main characteristics are Aluminium blades with black end caps Separated drive up to 20 meters Easy control from 0 to 100 in 10 steps Strong and robust fixation to walls Side view 30º vertical adjustment Top view pivoting function 34º and adju...

Page 6: ...120VAC I 50 60Hz Maximum speed 700rpm 450rpm 400rpm Protection degree IP55 IP55 IP55 Sound level 60dBA 60dBA 60dBA Total weight 55kg 78kg 91kg Motor type DC Brushless motor FAN PERFORMANCE Airflow 22 920m3 h 38 700m3 h 60 000m3 h Coverage 170m 280m 460m CONTROL Controller Control panel REGULATION Directives Low Voltage Directive 2014 35 EU Electromagnetic Compatibility 2014 30 EU Standards EN 6033...

Page 7: ...eces sent inside the boxes Please check the status and quantity of the fan equipment and the supporting parts immediately after you have opened the box to make sure that the goods received are in accordance with your order If parts are missing or damaged please inform our company s responsible person immediately for revision Wood box N Name Qty 1 Fan 1 pc 2 Control box 1 pc 3 Small equipment box S...

Page 8: ...from going under the fan It is recommended to fence at least four meters around the lifting equipment Follow any national or local regulation regarding installations in height SAFETY Ensure that the area chosen can hold the weight and torque of the fan and that there are no obstacles in its operating range Failure to do so may result in equipment damage or accident Ensure sign and protect the work...

Page 9: ...1 1 I Pillar Fixation The fan can be fixed with the steel I pillar by the adjustable standard clip as it is shown in the next figure 4 1 2 Sandwich Fixation The fan can be fixed with the square tube by the adjustable standard sandwich fixation as it is shown in the next figure Please use Bolt Kits 4xM12 45 According to the width of I Beam the corresponding hole position can be selected for clampin...

Page 10: ...ewed to the wall For these purposes the box has four holes in the corners The measurements of the box and perforations are detailed below CAUTION Install the control box in a safe area Failure to do so may result in equipment damage Install the control box at a distance less than 12 m from the fan Failure to do so the power supply of the equipment may be insufficient ...

Page 11: ...n cable cross sections and ambient temperature Copper 60 C 75 C conductors are recommended To ensure the fan operation the control box must be connected to the fan and the power supply The distance between the control box and the equipment must be less than 12 m and the cable with a minimum section of 1 5 mm2 Follow any national or local regulation regarding electrical installations CAUTION Follow...

Page 12: ... Modbus Configuration Parameters document provided by Anemoi The external control is connected direcly to the fan board using shielded cable type modbus RS485 2x2x0 50 mm POSCY The following figure shows the detail of the control connectors The electrical cables must be arranged in a separate circuit from the control cables to avoid interference Motor output line and oscillating function line Powe...

Page 13: ...ntroller is connected to the different by using control connections A B and GND The following figure shows the detail of the control connectors WARNING The earth meshes of each cable section must remain together Failure to do so may lead to communication errors Connect only one end of the earthing to the ground Failure to do so may lead to communication errors ...

Page 14: ...tube as shown below 3 Please keep always a distance of at least 20cm between the power and the data cable If both cables must cross at some point please ensure that they do so at a 90º angle to prevent interference WARNING Do not strip the communication cable more than 5cm Failure to do so may lead interferences Do not wind the unused communications cable Failure to do so may lead interferences Ma...

Page 15: ... data display as shown in table 3 Adjust the potentiometer to the required speed 4 Check the speed in the control screen To stop the fan perform the procedure in reverse NO DATA DISPLAY CONTENT Normal time Normal running state Failure time Failure for the fan Please refer to chapter 7 CAUTION Do not disconnect the fan for the current to start and stop the fan Otherwise the warranty would be voided...

Page 16: ...ting panel 7 2 The data display NO DISPLAY NAME FUNCTION 1 S 10 Gear numerical Display the gear value 2 M 0 Timing time Show how long the fan is turned off 3 OK STOP E IPM AUTO Start Stop Fail Show the fan state 4 60 Speed Show speed 5 26ºC Indoor temperature Display room temperature Control Panel Switch On Off Speed adjustment Settings Pivoting option ...

Page 17: ...wer connections E OC Overcurrent protection E UV Voltage below level Check input voltage more than 85V Check power connections E IPM Fail connexion Check the connections of wires Check power cable Rd ER E XT Communication error Check the communications wiring connections from the control screen to the power card E OT Excessive temperature Clean the dust from the control board and filter with a sof...

Page 18: ...Ensure that the fan does not make any noises or vibrations Check that the blades have not received any impact Yearly Check that there no alarms or faults in the variable speed drive located in the control box Ensure that the extension rod screws are properly tightened Ensure that the anchoring screws are properly tightened Check that the safety cable is properly fastened Check that the guy wires a...