RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
54
EN
HANCED
TEC
HNOLOGY
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-104/ Cyclic Period
Range
1~60000 sec
Default
60
Step
1 sec
Select the Cyclic Period.
It is to set interval time between Point set for Cyclic.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-104/ Time Out(t0)
Range
1~255 sec
Default
120
Step
1sec
Select the Timeout for connection establishment.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-104/ Time Out(t1)
Range
1~255 sec
Default
15
Step
1sec
Select the Timeout for send or test APDUs.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-104/ Time Out(t2)
Range
1~255 sec
Default
10
Step
1sec
Select the Timeout for acknowledgements in case of no data message
( t2<t1).
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-104/ Time Out(t3)
Range
1~255 sec
Default
20
Step
1sec
Select the Timeout for sending test frame in case of a long idle state.
COMMUNICATION/ PROTOCOL SETUP/ IEC60870-5-104/ Event Period
Range
0~255 sec
Default
5
Step
1
Select the delay time before events are sent. Single event or several
events occur and then if new event is not generated during the delay
time, the event(s) already generated is(are) sent to a Master.
[IEC60870-5-104]
>
Time Out(t2): 10
>
Time Out(t3): 20
>Event Period: 5
[IEC60870-5-104]
>
Time Out(t1): 15
>
Time Out(t2): 10
>Time Out(t3): 20
[IEC60870-5-104]
>
Time Out(t0): 120
>
Time Out(t1): 15
>Time Out(t2): 10
[IEC60870-5-104]
>
Time Out(t0): 120
>Time Out(t1): 15
>
Time Out(t2): 10
[IEC60870-5-104]
>Time Out(t0): 120
>
Time Out(t1): 15
>
Time Out(t2): 10
[IEC60870-5-104]
>
Function: DISABLE
>
ASDU Addr: 1
>Cyclic Period: 60