RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
102
EN
HANCED
TEC
HNOLOGY
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / Auto Rest’ T
Range
1.00 ~ 600.00 sec
Default
5.00
Step
0.01 sec
Auto Restoration Time :
Setting value is used in SEC, MID.
This is active when Program 2 on User Interface Panel is enabled.
SEC operates Loop control (Automatic Open) if a voltage selected
from “VRS – S/M” becomes dead line. After opened, the voltage
becomes Live Line, a certain period later, restores (Automatic Close).
MID, if a voltage selected form “VRS – S/M” becomes dead line, and
when Loop control (“Chg Alt-Tie” is on, it automatically changes to
Alternate Setting. After Loop control, Live Line becomes Tie Close,
and during operation, it figures as a fault and Trip Lockout. After it
becomes Live line, Restore (auto close and change to Primary setting).
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / DL V Max(%)
Range
20.0 ~ 70.0 %
Default
50.0
Step
0.1 %
Dead Bus Maximum Voltage(%) :
Sense Dead Line Voltage.
In Live Line, when a voltage is decreased below a set value, it
determines Dead Line.
In Source side, it is figured from a selected phase from “VS Wire”.
In Load side, it is figured from a selected phase from “VL Wire”.
PRIMARY SETTING / SYSTEM SETUP / LOOP CONTROL / LL V Min(%)
Range
50.0 ~ 85.0 %
Default
70.0
Step
0.1 %
Live Bus Minimum Voltage(%) :
Sense Live Line Voltage.
In Dead Line, when a voltage is increased over a set value, it
determines Live Line.
In Source side, it is figured form a selected phase from “VS Wire”,
In Load side, it is figured from a selected phase from “VL Wire”.
[LOOP CONTROL]
>LL V Min(%): 70.0
>
DL Pickup T: 50.00
>
LL Regain T: 10.00
[LOOP CONTROL]
>
OT Both DL: 10.00
>
Auto Rest’ T: 5.00
>DL V Max(%): 50.0
[LOOP CONTROL]
>
OT Both DL: 10.00
>Auto Rest’ T: 5.00
>
DL V Max(%): 50.0
Summary of Contents for EVRC2A-N6-NT
Page 2: ......