6.9. Set Group Change - Option
Sometimes, Recloser can be installed reversely against Power Flow(supply). In this case, it is
necessary to change Protection setting. EVRC2A has two options includes Primary Setting and
Alternate Setting to help in this situation. And these settings can be selected automatically by
“Set Group Change” function.
PRIMARY SETTING / SYSTEM SETUP / SET GROUP CHANGE / Function
Range
DISABLE,ENABLE
Default
DISABLE
Step
~
Set whether to use Set Group Change.
When this function is used, Primary setting is applied if power flow is
forward and Alternate setting is applied if power flow is
reverse(backward).
PRIMARY SETTING / SYSTEM SETUP/ SET GROUP CHANGE / Time interval
Range
10~180sec
Default
30
Step
1sec
If power flow is changed for this set time, setting group is changed.
Applying rules
y
This function is operated when Power line system is in normal condition. During fault
detecting(pickup status) or in fault condition, it does not work.
y
This function shall be operated when 3 phase voltages are more than 50% of rated voltage
and at least 1 phase has more than 10% of rated current.
[SET GROUP CHANGE]
>
Function: DISABLE
>Time interval: 30
[SET GROUP CHANGE]
>Function: DISABLE
>
Time interval: 30