PRIMARY SETTING / PROTECTION / INTERVALS / Reset T(LO)
Range
1.00 ~ 600.00 sec
Default
10.00
Step
0.01 sec
Select the Reset time for lockout.
The auto reclose logic is disabled for a setting time delay after the
recloser is manually/remotely closed. This prevents a fault from manual
reclosing. This delay must be longer than the trip time delay for any
protection not blocked after manual closing.
If no overcurrent trip occurs after a manual close and this timer expires,
the auto reclose logic automatically resets.
Traditionally, the Reset Time from lockout setting is set shorter than the
Reset time for auto reclose setting.
PRIMARY SETTING / PROTECTION / INTERVALS / C/P Wait
Range
1.00 ~ 600.00 sec
Default
60.00
Step
0.01 sec
Select the close power waiting time.
This timer is used to set the close power waiting time delay allowed to
reclose. It is activated when the reclose logic is in the reclose cycle
state. If this timer expires, the reclose logic is locked out.
[INTERVALS]
Reset T(AR): 30.00
Reset T(LO): 10.0
>C/P Wait: 60.00
[INTERVALS]
Reclose 4: 15.00
Reset T(AR): 30.00
>Reset T(LO): 10.00