RECLOSER CONTROL EVRC2A-N6,NT
http://www.entecene.co.kr
129
EN
HANCED
TEC
HNOLOGY
Phase Pickup Current Setup
The following setting is used to program the phase pickup current.
PRIMARY SETTING / PROTECTION / PICKUP CURRENT / Phase
Range
OFF, 10 ~ 1600A
Default
500
Step
1A
Set the pickup current of Phase Time Overcurrent elements.
Phase Fast Time Overcurrent Setup
The following setting is used to program the phase fast time overcurrent element.
PRIMARY SETTING / PROTECTION / PHASE FAST / Function
Range
TRIP, TR&AR
Default
TRIP
Step
~
If function = Trip
, the feature is operational. When the feature asserts
a TRIP condition, Trip operates.
If function = Trip & AR
, the feature is operational. When the feature
asserts a TRIP condition, TRIP and any other selected output relays
operate.
PRIMARY SETTING / PROTECTION / PHASE FAST / Relays(0-8)
Range
OFF, 0 ~ 8
Default
OFF
Step
1
Selects the relays required to operate when the feature generates a Trip.
Maximum 4 of Relay outputs can be selected to operate output signal.
0000(off) :
No Output Relay is selected.
1234 :
Operate output signal through 1, 2, 3, 4 Output Relay.
[PHASE FAST]
Function: TRIP
>Relays(0-8): OFF
Curve: ANSI-STI
[PHASE FAST]
>Function: TRIP
Relays(0-8): OFF
Curve: ANSI-STI
[PICKUP CURRENT(A)]
>Phase: 500
Ground: 250
S.E.F: OFF