3.15.7 15-2* Historic Log
View up to 50 logged data items via the array parameters
in this parameter group. Data is logged every time an
event occurs (not to be confused with SLC events). Events
in this context are defined as a change in 1 of the
following areas:
•
Digital inputs.
•
Digital outputs.
•
Warning word.
•
Alarm word.
•
Status word.
•
Control word.
•
Extended status word.
Events are logged with value and time stamp in ms. The
time interval between 2 events depends on how often
events occur (maximum once every scan time). Data
logging is continuous, but if an alarm occurs, the log is
saved and the values can be viewed on the display. This
feature is useful, for example when carrying out service
following a trip. View the historic log contained in this
parameter via the serial communication port or via the
display.
15-20 Historic Log: Event
Array [50]
Range:
Function:
0
*
[0 - 255 ]
View the event type of the logged events.
15-21 Historic Log: Value
Array [50]
Range:
Function:
0
*
[0 -
2147483647 ]
View the value of the logged event.
Interpret the event values according to
:
Digital input
Decimal value. See
for description after
converting to binary
value.
Digital output
(not
monitored in
this SW
release)
Decimal value. See
parameter 16-66 Digital
Output [bin]
for a
description after
converting to binary
value.
Warning word Decimal value. See
for a description.
Alarm word
Decimal value. See
for a description.
15-21 Historic Log: Value
Array [50]
Range:
Function:
Status word
Decimal value. See
for a description
after converting to binary
value.
Control word
Decimal value. See
for a description.
Extended
status word
Decimal value. See
parameter 16-94 Ext. Status
Word
for a description.
Table 3.30 Logged Events
15-22 Historic Log: Time
Array [50]
Range:
Function:
0 ms
*
[0 - 2147483647
ms]
View the time at which the logged
event occurred. Time is measured in
ms since frequency converter start. The
maximum value corresponds to
approximately 24 days, which means
that the count restarts at 0 after this
time period.
3.15.8 15-3* Alarm Log
Parameters in this group are array parameters where up to
10 fault logs can be viewed. 0 is the most recent logged
data, and 9 is the oldest. Fault codes, values, and time
stamp can be viewed for all logged data.
15-30 Fault Log: Error Code
Range:
Function:
0
*
[0 - 65535 ] View the fault code and look up its meaning in
15-31 Fault Log: Value
Array [10]
Range:
Function:
0
*
[-32767 - 32767 ] View an extra description of the error.
This parameter is mostly used with
alarm
38, internal fault
.
15-32 Fault Log: Time
Array [10]
Range:
Function:
0 s
*
[0 - 2147483647 s] View the time when the logged event
occurred. Time is measured in s from
frequency converter start-up.
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
206
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3