17-34 HIPERFACE Baudrate
Option:
Function:
NOTICE
This parameter cannot be adjusted while the
motor is running.
Select the baud rate of the attached encoder.
The parameter is only accessible when
parameter 17-20 Protocol Selection
is set to
[1]
HIPERFACE
.
[0]
600
[1]
1200
[2]
2400
[3]
4800
[4]
*
9600
[5]
19200
[6]
38400
3.17.3 17-5* Resolver Interface
This parameter group is used for setting parameters for the
VLT
®
Resolver Input MCB 103.
Usually, the resolver feedback is used as motor feedback
from permanent magnet motors with
parameter 1-01 Motor
Control Principle
set to
[3] Flux w/motor feedback
.
Resolver parameters cannot be adjusted while the motor is
running.
17-50 Poles
Range:
Function:
2
*
[2 - 8 ] Set the pole number on the resolver. The value is
stated in the datasheet for resolvers.
17-51 Input Voltage
Range:
Function:
7 V
*
[2 - 8 V] Set the input voltage to the resolver. The
voltage is stated as RMS value. The value is
stated in the datasheet for resolvers.
17-52 Input Frequency
Range:
Function:
10 kHz
*
[2 - 15 kHz] Set the input frequency to the resolver.
The value is stated in the datasheet for
resolvers.
17-53 Transformation Ratio
Range:
Function:
0.5
*
[0.1 - 1.1 ] Set the transformation ratio for the resolver.
The transformation ratio is:
T
ratio =
V
out
V
in
The value is stated in the datasheet for
resolvers.
17-56 Encoder Sim. Resolution
Set the resolution and activate the encoder emulation function
(generation of encoder signals from the measured position from
a resolver). Use this function to transfer the speed or position
information from 1 frequency converter to another. To disable
the function, select
[0] Disabled
.
Option:
Function:
[0]
*
Disabled
[1]
512
[2]
1024
[3]
2048
[4]
4096
17-59 Resolver Interface
Activate the VLT® Resolver Input MCB 103 when the resolver
parameters are selected. To avoid damage to resolvers, adjust
parameter
parameter 17-53 Transformation
before enabling this parameter.
Option:
Function:
[0]
*
Disabled
[1]
Enabled
3.17.4 17-6* Monitoring and Application
This parameter group is for selecting extra functions when
VLT
®
Encoder Input MCB 102 or VLT
®
Resolver Input MCB
103 is fitted into option slot B as speed feedback.
Monitoring and application parameters cannot be adjusted
while the motor is running.
17-60 Feedback Direction
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Change the detected encoder rotation
direction without changing the wiring to
the encoder.
[0]
*
Clockwise
[1]
Counter
clockwise
17-61 Feedback Signal Monitoring
Select which action the frequency converter should take if a
faulty encoder signal is detected. The encoder function in
parameter 17-61 Feedback Signal Monitoring is an electrical
check of the hardware circuit in the encoder system.
Option:
Function:
[0]
Disabled
[1]
*
Warning
[2]
Trip
[3]
Jog
[4]
Freeze Output
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
218
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02