8-13 Configurable Status Word STW
This is an array parameter with 16 elements, 1 element for each
bit in range 0–15. Elements 5 and 11–15 are configurable. Each
of the bits can be configured to any of the following options.
Option:
Function:
[2]
Alarm 68 Only
The input goes high whenever
alarm 68, Safe Torque Off
activated
is active and goes low
whenever
alarm 68, Safe Torque
Off activated
is not active.
[3]
Trip excl Alarm 68
[4]
Position Tracking
[5]
Position Limit
[6]
Touch on Target
[7]
Touch Activated
[10]
T18 DI status
[11]
T19 DI status
[12]
T27 DI status
[13]
T29 DI status
[14]
T32 DI status
[15]
T33 DI status
[16]
T37 DI status
The input goes high whenever
terminal 37 has 0 V and goes
low whenever terminal 37 has
24 V.
[17]
X30/2 DI status
[18]
X30/3 DI status
[19]
X30/4 DI status
[20]
CTW Timeout Toggle
Inverse
[21]
Thermal warning
[30]
Brake fault (IGBT)
[40]
Out of ref range
[49]
Derate active
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic Rule 0
[71]
Logic Rule 1
[72]
Logic Rule 2
[73]
Logic Rule 3
[74]
Logic Rule 4
[75]
Logic Rule 5
[80]
SL digital out A
[81]
SL digital out B
[82]
SL digital out C
[83]
SL digital out D
[84]
SL digital out E
[85]
SL digital out F
[86]
ATEX ETR cur. alarm
[87]
ATEX ETR freq. alarm
8-13 Configurable Status Word STW
This is an array parameter with 16 elements, 1 element for each
bit in range 0–15. Elements 5 and 11–15 are configurable. Each
of the bits can be configured to any of the following options.
Option:
Function:
[88]
ATEX ETR cur. warning
[89]
ATEX ETR freq. warning
[90]
Safe Function active
[91]
Safe Opt. Reset req.
[92]
IGBT-cooling
See
parameter group 5-3* Digital
Outputs
.
[181] Prev. Maintenance
[200] User Defined Alerts
[231] In Power Lim. Mot.
See
parameter group 4-8* Power
Limit
. Use this option in motor
mode only.
[232] In Power Lim. Gen.
See
parameter group 4-8* Power
Limit
. Use this option in
generating mode only.
[233] In Power Limit
See
parameter group 4-8* Power
Limit
. Use this option in both
the motor and the generating
modes.
8-13 Configurable Status Word STW
Option:
Function:
NOTICE
Options in this block are
only available for
software version 8.XX.
[0]
No function
The input is always low.
[1]
Profile Default
Depended on the profile set
in
parameter 8-10 Control
Profile
.
[2]
Alarm 68 Only
The input goes high
whenever Alarm 68 is active
and goes low whenever no
alarm 68 is activated
[3]
Trip excl Alarm 68
[10]
T18 DI status
[11]
T19 DI status
[12]
T27 DI status
[13]
T29 DI status
[14]
T32 DI status
[15]
T33 DI status
[16]
T37 DI status
The input goes high
whenever T37 has 0 V and
goes low whenever T37 has
24 V.
[20]
CTW Timeout Toggle
Inverse
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
156
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02