Manual initialization
1.
Disconnect from mains and wait until the display
turns off.
2.
2a
Press [Status] - [Main Menu] - [OK] at
the same time while powering up the
LCP 102, graphical display.
2b
Press [Menu] - [OK] while powering up
the LCP 101, numerical display.
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
This procedure initializes all except:
•
Parameter 15-00 Operating hours
.
•
Parameter 15-03 Power Up's
.
•
Parameter 15-04 Over Temp's
.
•
Parameter 15-05 Over Volt's
.
NOTICE
A manual initialization also resets serial communication,
RFI filter settings (
parameter 14-50 RFI Filter
), and fault
log settings.