5-40 Function Relay
Option:
Function:
[121] Remote ref active
Output is high when
=
[1]
Remote
or
[0] Linked to hand/auto
while
the LCP is in
auto-on
mode. See
[122] No alarm
Output is high when no alarm is
present.
[123] Start command
activ
Output is high when the start
command is high (that is via digital
input, bus connection, [Hand On], or
[Auto On]), and a stop has been last
command.
[124] Running reverse
Output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
running
AND
reverse
).
[125] Drive in hand
mode
Output is high when the frequency
converter is in
hand-on
mode (as
indicated by the LED light above
[Hand On]).
[126] Drive in auto
mode
Output is high when the frequency
converter is in
auto-on
mode (as
indicated by LED on above [Auto On]).
[151] ATEX ETR cur.
alarm
Selectable if
is set to
[20] ATEX
ETR
or
[21] Advanced ETR
. If
alarm 164,
ATEX ETR cur.lim.alarm
is active, the
output is 1.
[152] ATEX ETR freq.
alarm
Selectable if
is set to
[20] ATEX
ETR
or
[21] Advanced ETR
. If
alarm 166,
ATEX ETR freq.lim.alarm
is active, the
output is 1.
[153] ATEX ETR cur.
warning
Selectable if
is set to
[20] ATEX
ETR
or
[21] Advanced ETR
. If
alarm 163,
ATEX ETR cur.lim.warning
is active, the
output is 1.
[154] ATEX ETR freq.
warning
Selectable if
is set to
[20] ATEX
ETR
or
[21] Advanced ETR
. If
warning
165, ATEX ETR freq.lim.warning
is active,
the output is 1.
[180] Clock Fault
[181] Prev. Maintenance
[188] AHF Capacitor
Connect
[189] External Fan
Control
The internal logics for the internal fan
control is transferred to this output to
make it possible to control an external
fan (relevant for HP duct cooling).
5-40 Function Relay
Option:
Function:
[190] Safe Function
active
[191] Safe Opt. Reset
req.
[192] RS Flipflop 0
See
parameter group 13-1*
Comparators
.
[193] RS Flipflop 1
See
parameter group 13-1*
Comparators
.
[194] RS Flipflop 2
See
parameter group 13-1*
Comparators
.
[195] RS Flipflop 3
See
parameter group 13-1*
Comparators
.
[196] RS Flipflop 4
See
parameter group 13-1*
Comparators
.
[197] RS Flipflop 5
See
parameter group 13-1*
Comparators
.
[198] RS Flipflop 6
See
parameter group 13-1*
Comparators
.
[199] RS Flipflop 7
See
parameter group 13-1*
Comparators
.
[221] IGBT-cooling
Use this option for handling the
overcurrent trips. When the frequency
converter detects an overcurrent
condition, it shows
alarm 13,
Overcurrent
and triggers a reset. If the
overcurrent condition occurs the 3rd
time in a row, the frequency converter
shows
alarm 13, Overcurrent
and
initiates a 3 minute delay before the
next reset.
[222] Homing OK
NOTICE
This option is available only with
software version 48.XX.
Homing is completed with the selected
homing function
(
parameter 17-80 Homing Function
).
[223] On Target
NOTICE
This option is available only with
software version 48.XX.
Positioning is completed and the on
target signal is sent when the actual
position is within
for the duration of
and the
actual speed does not exceed
parameter 3-05 On Reference Window
.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
127
3
3