13-01 Start Event
Select the boolean (true or false) input to activate smart logic
control.
Option:
Function:
[4]
On reference
The motor runs on reference.
[5]
Torque limit
The torque limit set in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Torque Limit Generator
is exceeded.
[6]
Current Limit
The motor current limit set in
is exceeded.
[7]
Out of current
range
The motor current is outside the range
set in
.
[8]
Below I low
The motor current is lower than set in
parameter 4-50 Warning Current Low
[9]
Above I high
The motor current is higher than set in
parameter 4-51 Warning Current High
.
[10]
Out of speed
range
The speed is outside the range set in
parameter 4-52 Warning Speed Low
and
parameter 4-53 Warning Speed High
.
[11]
Below speed
low
The output speed is lower than the
setting in
[12]
Above speed
high
The output speed is higher than the
setting in
[13]
Out of feedb.
range
The feedback is outside the range set in
parameter 4-56 Warning Feedback Low
and
parameter 4-57 Warning Feedback
High
.
[14]
Below feedb.
low
The feedback is below the limit set in
parameter 4-56 Warning Feedback Low
.
[15]
Above feedb.
high
The feedback is above the limit set in
parameter 4-57 Warning Feedback High
.
[16]
Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the
brake resistor, or the thermistor.
[17]
Mains out of
range
The mains voltage is outside the
specified voltage range.
[18]
Reversing
The output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
running AND reverse).
[19]
Warning
A warning is active.
[20]
Alarm (trip)
A (trip) alarm is active.
[21]
Alarm (trip lock) A (trip lock) alarm is active.
[22]
Comparator 0
Use the result of comparator 0.
[23]
Comparator 1
Use the result of comparator 1.
13-01 Start Event
Select the boolean (true or false) input to activate smart logic
control.
Option:
Function:
[24]
Comparator 2
Use the result of comparator 2.
[25]
Comparator 3
Use the result of comparator 3.
[26]
Logic rule 0
Use the result of logic rule 0.
[27]
Logic rule 1
Use the result of logic rule 1.
[28]
Logic rule 2
Use the result of logic rule 2.
[29]
Logic rule 3
Use the result of logic rule 3.
[33]
Digital input
DI18
Use the result of digital input 18.
[34]
Digital input
DI19
Use the result of digital input 19.
[35]
Digital input
DI27
Use the result of digital input 27.
[36]
Digital input
DI29
Use the result of digital input 29.
[37]
Digital input
DI32
Use the result of digital input 32.
[38]
Digital input
DI33
Use the result of digital input 33.
[39]
Start command
A start command is issued.
[40]
Drive stopped
A stop command (jog, stop, quick stop,
coast) is issued – and not from the SLC
itself.
[41]
Reset Trip
A reset is issued.
[42]
Auto-reset Trip
An auto reset is performed.
[43]
Ok key
[OK] is pressed. Only available on the
graphical LCP.
[44]
Reset key
[Reset] is pressed. Only available on the
graphical LCP.
[45]
Left key
[
◄
] is pressed. Only available on the
graphical LCP.
[46]
Right key
[
►
] is pressed. Only available on the
graphical LCP.
[47]
Up key
[
▲
] is pressed. Only available on the
graphical LCP.
[48]
Down key
[
▼
] is pressed. Only available on the
graphical LCP.
[50]
Comparator 4
Use the result of comparator 4.
[51]
Comparator 5
Use the result of comparator 5.
[60]
Logic rule 4
Use the result of logic rule 4.
[61]
Logic rule 5
Use the result of logic rule 5.
[76]
Digital input
x30/2
Use the value of x30/2 (VLT
®
General
Purpose I/O MCB 101).
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
167