4-50 Warning Current Low
Range:
Function:
0 A
*
[ 0 - par.
4-51 A]
Enter the I
LOW
value. When the motor current
falls below this limit, the display reads
Current
Low
. The signal outputs can be programmed to
produce a status signal on terminal 27 or 29 (FC
302 only) and on relay output 01 or 02 (FC 302
only). Refer to
.
4-51 Warning Current High
Range:
Function:
Size
related
*
[ par.
4-50 - par.
16-37 A]
Enter the I
HIGH
value. When the motor
current exceeds this limit, the display
reads
Current High
. The signal outputs can
be programmed to produce a status
signal on terminal 27 or 29 (FC 302 only)
and on relay output 01 or 02 (FC 302
only). Refer to
.
4-52 Warning Speed Low
Range:
Function:
0 RPM
*
[ 0 - par.
4-53 RPM]
Enter the n
LOW
value. When the motor speed
exceeds this limit, the display reads
Speed
low
. The signal outputs can be programmed
to produce a status signal on terminal 27 or
29 (FC 302 only) and on relay output 01 or
02 (FC 302 only).
4-53 Warning Speed High
Range:
Function:
Size
related
*
[ par.
4-52 -
60000
RPM]
Enter the n
HIGH
value. When the motor
speed exceeds this value, the display
reads
Speed high
. The signal outputs can
be programmed to produce a status
signal on terminals 27 or 29 and on relay
outputs 01 or 02. Refer to
4-54 Warning Reference Low
Range:
Function:
-999999.999
*
[ -999999.999 -
par. 4-55 ]
Enter the lower reference limit.
When the actual reference drops
below this limit, the display
indicates
Ref
LOW
. The signal
outputs can be programmed to
produce a status signal on
terminal 27 or 29 (FC 302 only)
and on relay output 01 or 02 (FC
302 only).
4-55 Warning Reference High
Range:
Function:
999999.999
*
[ par. 4-54 -
999999.999 ]
Enter the upper reference limit.
When the actual reference exceeds
this limit, the display reads Ref
high
.
4-55 Warning Reference High
Range:
Function:
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 (FC 302
only) and on relay output 01 or 02
(FC 302 only).
4-56 Warning Feedback Low
Range:
Function:
Size
related
*
[ -999999.999 -
par. 4-57
ReferenceFeed-
backUnit]
Enter the lower feedback limit.
When the feedback drops below
this limit, the display reads
Feedb
Low
. The signal outputs can
be programmed to produce a
status signal on terminal 27 or
29 (FC 302 only) and on relay
output 01 or 02 (FC 302 only).
4-57 Warning Feedback High
Range:
Function:
Size
related
*
[ par. 4-56 -
999999.999
ReferenceFeed-
backUnit]
Enter the upper feedback limit.
When the feedback exceeds this
limit, the display reads Feedb
High
.
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 (FC
302 only) and on relay output 01
or 02 (FC 302 only).
4-58 Missing Motor Phase Function
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
The missing motor phase function detects
whether the motor phase is missing during
motor rotation. Shows alarm 30, 31, or 32 in the
event of a missing motor phase. Enable this
function to avoid motor damage.
See also
chapter 3.5.5 Combinations of parameters
[0] Disabled
The frequency converter does not issue a missing
motor phase alarm. Not recommended due to
risk of motor damage.
[1] Trip 100
ms
For a quick detection time and alarm in the
event of a missing motor phase.
[2] Trip 1000
ms
[3] Trip
100ms
3ph
detec.
Special option relevant for crane applications
when lowering a small load that lets the
frequency converter avoid false detections of
missing motor phase.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
93
3
3