7-05 Speed PID Diff. Gain Limit
5 N/A
All set-ups
TRUE
-1
Uint16
7-06 Speed PID Lowpass Filter Time
ExpressionLimit
All set-ups
TRUE
-4
Uint16
7-07 Speed PID Feedback Gear Ratio
1 N/A
All set-ups
FALSE
-4
Uint32
7-08 Speed PID Feed Forward Factor
0 %
All set-ups
FALSE
0
Uint16
7-09 Speed PID Error Correction w/ Ramp
ExpressionLimit
All set-ups
TRUE
67
Uint32
7-1* Torque PI Ctrl.
7-10 Torque PI Feedback Source
[0] Controller Off
All set-ups
TRUE
-
Uint8
7-12 Torque PI Proportional Gain
100 %
All set-ups
TRUE
0
Uint16
7-13 Torque PI Integration Time
0.020 s
All set-ups
TRUE
-3
Uint16
7-16 Torque PI Lowpass Filter Time
5 ms
All set-ups
TRUE
-4
Uint16
7-18 Torque PI Feed Forward Factor
0 %
All set-ups
TRUE
0
Uint16
7-19 Current Controller Rise Time
ExpressionLimit
All set-ups
TRUE
0
Uint16
7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource
[0] No function
All set-ups
TRUE
-
Uint8
7-22 Process CL Feedback 2 Resource
[0] No function
All set-ups
TRUE
-
Uint8
7-3* Process PID Ctrl.
7-30 Process PID Normal/ Inverse Control
[0] Normal
All set-ups
TRUE
-
Uint8
7-31 Process PID Anti Windup
[1] On
All set-ups
TRUE
-
Uint8
7-32 Process PID Start Speed
0 RPM
All set-ups
TRUE
67
Uint16
7-33 Process PID Proportional Gain
ExpressionLimit
All set-ups
TRUE
-2
Uint16
7-34 Process PID Integral Time
10000 s
All set-ups
TRUE
-2
Uint32
7-35 Process PID Differentiation Time
0 s
All set-ups
TRUE
-2
Uint16
7-36 Process PID Diff. Gain Limit
5 N/A
All set-ups
TRUE
-1
Uint16
7-38 Process PID Feed Forward Factor
0 %
All set-ups
TRUE
0
Uint16
7-39 On Reference Bandwidth
5 %
All set-ups
TRUE
0
Uint8
7-4* Adv. Process PID I
7-40 Process PID I-part Reset
[0] No
All set-ups
TRUE
-
Uint8
7-41 Process PID Output Neg. Clamp
-100 %
All set-ups
TRUE
0
Int16
7-42 Process PID Output Pos. Clamp
100 %
All set-ups
TRUE
0
Int16
7-43 Process PID Gain Scale at Min. Ref.
100 %
All set-ups
TRUE
0
Int16
7-44 Process PID Gain Scale at Max. Ref.
100 %
All set-ups
TRUE
0
Int16
7-45 Process PID Feed Fwd Resource
[0] No function
All set-ups
TRUE
-
Uint8
7-46 Process PID Feed Fwd Normal/ Inv. Ctrl.
[0] Normal
All set-ups
TRUE
-
Uint8
7-48 PCD Feed Forward
0 N/A
All set-ups
x
TRUE
0
Uint16
7-49 Process PID Output Normal/ Inv. Ctrl.
[0] Normal
All set-ups
TRUE
-
Uint8
7-5* Adv. Process PID II
7-50 Process PID Extended PID
[1] Enabled
All set-ups
TRUE
-
Uint8
7-51 Process PID Feed Fwd Gain
1 N/A
All set-ups
TRUE
-2
Uint16
7-52 Process PID Feed Fwd Ramp up
0.01 s
All set-ups
TRUE
-2
Uint32
7-53 Process PID Feed Fwd Ramp down
0.01 s
All set-ups
TRUE
-2
Uint32
7-56 Process PID Ref. Filter Time
0.001 s
All set-ups
TRUE
-3
Uint16
7-57 Process PID Fb. Filter Time
0.001 s
All set-ups
TRUE
-3
Uint16
7-9* Position PI Ctrl.
7-90 Position PI Feedback Source
[0] Motor feedb. P1-02
All set-ups
TRUE
-
Uint8
7-91 Position PI Droop
0.0 °
All set-ups
TRUE
-1
Uint16
7-92 Position PI Proportional Gain
0.0150 N/A
All set-ups
TRUE
-4
Uint32
7-93 Position PI Integral Time
20000.0 ms
All set-ups
TRUE
-4
Uint32
7-94 Position PI Feedback Scale Numerator
1 N/A
All set-ups
TRUE
0
Int32
7-95 Position PI Feebback Scale Denominator
1 N/A
All set-ups
TRUE
0
Int32
7-97 Position PI Max Speed Above Master
100 RPM
All set-ups
TRUE
67
Uint16
7-98 Position PI Feed Forward Factor
98 %
All set-ups
TRUE
0
Uint16
7-99 Position PI Minimum Ramp Time
0.010 s
All set-ups
TRUE
-3
Uint32
Parameter Lists
VLT
®
AutomationDrive FC 301/302
302
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
5
5
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......