13-44 Logic Rule Boolean 3
Array [6]
Option:
Function:
[222] Homing Ok
NOTICE
This option is available only with
software version 48.20 and
newer.
Homing is completed with the
selected homing function
(
parameter 17-80 Homing Function
[223] On Target
NOTICE
This option is available only with
software version 48.20 and
newer.
Positioning is completed and the on-
target signal is sent when the actual
position is within
for the duration of
and the
actual speed does not exceed
parameter 3-05 On Reference Window
[224] Position Error
NOTICE
This option is available only with
software version 48.20 and
newer.
The position error exceeds the value
in
parameter 4-71 Maximum Position
for the time set in
parameter 4-72 Position Error Timeout
[225] Position Limit
NOTICE
This option is available only with
software version 48.20 and
newer.
The position is outside the limits set
in
parameter 3-06 Minimum Position
and
parameter 3-07 Maximum Position
.
[226] Touch on Target
NOTICE
This option is available only with
software version 48.20 and
newer.
Target position is reached in touch
probe position mode.
[227] Touch Activated
NOTICE
This option is available only with
software version 48.20 and
newer.
13-44 Logic Rule Boolean 3
Array [6]
Option:
Function:
Touch probe positioning active. The
frequency converter monitors the
touch probe sensor input.
3.13.10 13-5* States
13-51 SL Controller Event
Option:
Function:
[0]
False
Select the boolean input (true or false)
to define the smart logic controller
event. See
parameter 13-01 Start Event
(options
[0] False
–
[61] Logic rule 5
) and
parameter 13-02 Stop Event
(options
[70] SL Time-out 3
–
[74] SL Time-out 7
)
for more information.
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb.
range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
184
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3