13-10 Comparator Operand
Option:
Function:
logical product of the status bits running
AND reverse).
[56]
In range
The motor runs within the programmed
current and speed ranges set in
parameter 4-50 Warning Current Low
to
parameter 4-53 Warning Speed High
.
[60]
On reference
The motor runs on reference.
[61]
Below
reference, low
The motor runs at a reference which is
less than the value in
parameter 4-54 Warning Reference Low
[62]
Above ref, high The motor runs at a reference which
exceeds the value in
parameter 4-55 Warning Reference High
[65]
Torque limit
The torque exceeds the value in
parameter 4-16 Torque Limit Motor Mode
or
parameter 4-17 Torque Limit Generator
Mode
.
[66]
Current Limit
The motor current exceeds the value in
[67]
Out of current
range
The motor current is outside the range
set in
[68]
Below I low
The motor current is lower than the
value in
parameter 4-50 Warning Current
[69]
Above I high
The motor current is higher than the
value in
parameter 4-51 Warning Current
.
[70]
Out of speed
range
The speed is outside the range set in
parameter 4-52 Warning Speed Low
and
parameter 4-53 Warning Speed High
.
[71]
Below speed
low
The output speed is lower than the value
in
parameter 4-52 Warning Speed Low
[72]
Above speed
high
The output speed is higher than the
value in
.
[75]
Out of feedback
range
The feedback is outside the range set in
parameter 4-56 Warning Feedback Low
and
parameter 4-57 Warning Feedback
High
.
[76]
Below feedback
low
The feedback is lower than the limit set
in
parameter 4-56 Warning Feedback Low
.
[77]
Above feedback
high
The feedback exceeds the limit set in
parameter 4-57 Warning Feedback High
[80]
Thermal
warning
This operand becomes true when the
frequency converter detects any thermal
warning, for instance when the
temperature exceeds the limit in the
13-10 Comparator Operand
Option:
Function:
motor, the frequency converter, the brake
resistor, or thermistor.
[82]
Mains out of
range
The mains voltage is outside the
specified voltage range.
[85]
Warning
If a warning is triggered, this operand
gets the warning number.
[86]
Alarm (trip)
A trip alarm is active.
[87]
Alarm (trip lock) A trip lock alarm is active.
[90]
Bus OK
Active communication (no timeout) via
the serial communication port.
[91]
Torque limit &
stop
If the frequency converter has received a
stop signal and is at the torque limit, the
signal is logic 0.
[92]
Brake fault
(IGBT)
The brake IGBT is short-circuited.
[93]
Mech. brake
control
The mechanical brake is active.
[94]
Safe stop active
[100] Comparator 0
The result of comparator 0.
[101] Comparator 1
The result of comparator 1.
[102] Comparator 2
The result of comparator 2.
[103] Comparator 3
The result of comparator 3.
[104] Comparator 4
The result of comparator 4.
[105] Comparator 5
The result of comparator 5.
[110] Logic rule 0
The result of logic rule 0.
[111] Logic rule 1
The result of logic rule 1.
[112] Logic rule 2
The result of logic rule 2.
[113] Logic rule 3
The result of logic rule 3.
[114] Logic rule 4
The result of logic rule 4.
[115] Logic rule 5
The result of logic rule 5.
[120] SL Time-out 0
The result of SLC timer 0.
[121] SL Time-out 1
The result of SLC timer 1.
[122] SL Time-out 2
The result of SLC timer 2.
[123] SL Time-out 3
The result of SLC timer 3.
[124] SL Time-out 4
The result of SLC timer 4.
[125] SL Time-out 5
The result of SLC timer 5.
[126] SL Time-out 6
The result of SLC timer 6.
[127] SL Time-out 7
The result of SLC timer 7.
[130] Digital input
DI18
Digital input 18 (high=true).
[131] Digital input
DI19
Digital input 19 (high=true).
[132] Digital input
DI27
Digital input 27 (high=true).
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
171
3
3