8-05 End-of-Timeout Function
Select the action after receiving a valid control word following a
timeout.
This parameter is active only when
is set to:
•
[7] Set-up 1
.
•
[8] Set-up 2
.
•
[9] Set-up 3
.
•
[10] Set-up 4
.
Option:
Function:
[0]
Hold set-up
Retains the set-up selected in
parameter 8-04 Control Word Timeout
Function
and shows a warning until
parameter 8-06 Reset Control Word
Timeout
toggles. Then the frequency
converter resumes its original set-
up.
[1]
*
Resume set-up
Resumes the set-up that was active
before the timeout.
8-06 Reset Control Word Timeout
This parameter is active only when
[0] Hold set-up
has been
selected in
parameter 8-05 End-of-Timeout Function
.
Option:
Function:
[0]
*
Do not reset Retains the set-up specified in
parameter 8-04 Control Word Timeout Function
following a control word timeout.
[1]
Do reset
Restores the frequency converter to the
original set-up following a control word
timeout. The frequency converter performs
the reset and then immediately reverts to the
[0] Do not reset
setting.
8-07 Diagnosis Trigger
This parameter has no function for DeviceNet.
Option:
Function:
[0]
*
Disable
[1]
Trigger on alarms
[2]
Trigger alarm/warn.
8-08 Readout Filtering
Use this function if the speed feedback value readouts on the
fieldbus fluctuate. Select
[1] Motor Data LP-Filter
if the function is
required. A power cycle is required for changes to take effect.
Option:
Function:
[0] Motor Data
Std-Filt.
Normal fieldbus readouts.
[1] Motor Data LP-
Filter
Filtered fieldbus readouts of the following
parameters:
•
•
.
•
8-08 Readout Filtering
Use this function if the speed feedback value readouts on the
fieldbus fluctuate. Select
[1] Motor Data LP-Filter
if the function is
required. A power cycle is required for changes to take effect.
Option:
Function:
•
•
•
.
•
•
Parameter 16-25 Torque [Nm] High
.
3.9.2 8-1* Ctrl. Word Settings
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A are visible in the LCP display.
For guidelines in selection of
[0] FC profile
and
[1] PROFIdrive
profile
, refer to the
design guide
.
For more guidelines in the selection of
[1] PROFIdrive profile
, refer
to the
installation guide
for the installed fieldbus.
Option:
Function:
[0] FC profile
[1] PROFIdrive profile
[3] FC Motion Profile
NOTICE
This option is available only with
software version 48.XX.
Assigns motion-specific functions to
various control and status word bits. This
option is available when
[9] Positioning
or
[10] Synchronization
is selected in
parameter 1-00 Configuration Mode
.
[5] ODVA
[7] CANopen DSP 402
[8] MCO
8-13 Configurable Status Word STW
This is an array parameter with 16 elements, 1 element for each
bit in range 0–15. Elements 5 and 11–15 are configurable. Each
of the bits can be configured to any of the following options.
Option:
Function:
NOTICE
Options in this block are
only available for 48.XX.
[0]
No function
The input is always low.
[1]
Profile Default
Depending on the profile set in
parameter 8-10 Control Word
Profile
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
155
3
3