8-14 Configurable Control Word CTW
This is an array parameter with 16 elements, 1 element for each
bit in range 0–15. Each of the bits can be configured to any of
the following options.
Option:
Function:
[18]
Virtual Master
Starts the virtual master configured in
parameter 3-27 Virtual Master Max Ref
.
[19]
Enable Master
Offset
Activates the master offset selected in
when
parameter 17-93 Master Offset Selection
has a selection from
[1] Absolute
to
[5]
Relative Touch Sensor
.
[20]
Control Word
Toggle
Command
[21]
Target Inverse
Changes the sign of the set target
position. For example, if the set target is
1000, the activation of this option
changes the value to -1000.
[22]
Digital Out 27
[23]
Digital Out 29
[24]
Digital Out
X30/6
[25]
Digital Out
X30/7
[26]
Home Sensor
Home sensor connected via fieldbus
master.
NOTICE
Accuracy of home position
depends on delay in transferring
the signals.
[27]
Touch Sensor
Touch sensor connected via fieldbus
master.
NOTICE
Accuracy of touch probe
positioning depends on delay in
transferring the signals.
[78]
Reset Preventive
Maintenance
Word
[231] Power Limit
Mot.
See
parameter group 4-8* Power Limit
.
Use this option in the motor mode only.
[232] Power Limit
Gen.
See
parameter group 4-8* Power Limit
.
Use this option in the generating mode
only.
[233] Power Limit
Both
See
parameter group 4-8* Power Limit
.
Use this option in both the motor and
the generating modes.
8-14 Configurable Control Word CTW
Option:
Function:
Selection of control word bit 10 if it is
active low or active high
NOTICE
Options in this block are only
available for software version 8.XX.
[0]
None
The frequency converter ignores the
information in this bit.
[1]
*
Profile default
The functionality of the bit depends on
the selection in
parameter 8-10 Control
Word Profile
.
[2]
CTW Valid,
active low
If set to 1, the frequency converter
ignores the remaining bits of the control
word.
[3]
Safe Option
Reset
This function is only available in bits 12–
15 of the control word if a safety option
is mounted in the frequency converter.
The reset is executed on a 0
⇒
1 transition
and resets the safety option as set in
parameter 42-24 Restart Behaviour
.
[4]
PID error
inverse
Inverts the resulting error from the
process PID controller. Available only if
parameter 1-00 Configuration Mode
is set
to
[6] Surface Winder
,
[7] Extended PID
Speed OL
, or
[8] Extended PID Speed CL
.
[5]
PID reset I part Resets the I-part of the process PID
controller. Equivalent to
parameter 7-40 Process PID I-part Reset
.
Available only if
parameter 1-00 Configu-
ration Mode
is set to
[6] Surface Winder
,
[7] Extended PID Speed OL
, or
[8] Extended
PID Speed CL
.
[6]
PID enable
Enables the extended process PID
controller. Equivalent to
parameter 7-50 Process PID Extended PID
.
Available only if
parameter 1-00 Configu-
ration Mode
is set to
[6] Surface Winder
,
[7] Extended PID Speed OL
, or
[8] Extended
PID Speed CL
.
[7]
External
Interlock
[10]
Bit 10 = 0 >
CTW Timeout
[20]
Control Word
Toggle
Command
Changes the sign of the set target
position. For example, if the set target is
1000, the activation of this option
changes the value to -1000.
[78]
Reset
Preventive
Maintenance
Word
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
158
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02