8-42 PCD Write Configuration
Range:
Function:
Size
related
*
[0 -
9999 ]
Select the parameters to be assigned to
the PCD's telegrams. The number of
available PCDs depends on the telegram
type. The values in the PCDs are then
written to the selected parameters as
data values.
8-43 PCD Read Configuration
Range:
Function:
Size
related
*
[0 -
9999 ]
Select the parameters to be assigned to
the PCDs of the telegrams. The number
of available PCDs depends on the
telegram type. PCDs contain the actual
data values of the selected parameters.
8-45 BTM Transaction Command
Option:
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
[0]
*
Off
[1]
Start Transaction
[2]
Commit transaction
[3]
Clear error
8-46 BTM Transaction Status
Option:
Function:
[0]
*
Off
[1]
Transaction Started
[2]
Transaction Comitting
[3]
Transaction Timeout
[4]
Err. Non-existing Par.
[5]
Err. Par. Out of Range
[6]
Transaction Failed
[7]
SO Config Check
[8]
SO Config Check Done
8-47 BTM Timeout
Range:
Function:
60 s
*
[1 - 360 s] Select the BTM timeout after a BTM
transaction has been started.
8-48 BTM Maximum Errors
Range:
Function:
21
*
[0 - 21 ] Selects the maximum allowed number of bulk
transfer mode errors before aborting. If it is set to
maximum, there is no abort.
8-49 BTM Error Log
Range:
Function:
0.255
*
[0.000 -
9999.255 ]
List of parameters that failed during
bulk transfer mode. The value after the
decimal break is the fault code (255
stands for no error).
3.9.5 8-5* Digital/Bus
Parameters for configuring the control word merging.
NOTICE
These parameters are active only when
parameter 8-01 Control Site
is set to
[0] Digital and control
word
.
8-50 Coasting Select
Select the trigger for the coasting function.
Option:
Function:
[0]
Digital input A digital input triggers the coasting function.
[1]
Bus
A serial communication port or the fieldbus
triggers the coasting function.
[2]
Logic AND
The fieldbus/serial communication port and a
digital input trigger the coasting function.
[3]
*
Logic OR
The fieldbus/serial communication port or a
digital input triggers the coasting function.
8-51 Quick Stop Select
Select the trigger for the quick stop function.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-52 DC Brake Select
Select control of the DC brake via the terminals (digital input)
and/or via the fieldbus.
Option:
Function:
NOTICE
When
parameter 1-10 Motor Construction
is set to
[1] PM non-salient SPM
, only
selection
[0] Digital input
is available.
[0] Digital input Activate a start command via a digital input.
[1] Bus
Activate a start command via the serial
communication port or fieldbus option.
[2] Logic AND
Activate a start command via the fieldbus/serial
communication port and also via 1 of the
digital inputs.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
163