36-60 Terminal X49/11 Analogue Output
Select the functionality of terminal X49/11.
Option:
Function:
[141]
Bus ctrl 0-20mA t.o.
36-62 Terminal X49/11 Min. Scale
Range:
Function:
0 %
*
[0 -
200 %]
Match the minimum output of terminal
X49/11 with a required value. For more
information, see
.
36-63 Terminal X49/11 Max. Scale
Range:
Function:
100 %
*
[0 -
200 %]
Scale the maximum output of terminal
X49/11. For more information, see
parameter 36-43 Terminal X49/7 Max. Scale
36-64 Terminal X49/11 Bus Control
Range:
Function:
0 %
*
[0 - 100 %] This parameter contains the output level of
terminal X49/11 if the terminal is controlled
by a fieldbus.
36-65 Terminal X49/11 Timeout Preset
Range:
Function:
0 %
*
[0 - 100 %] The frequency converter sends the value of
this parameter to the output terminal when
the terminal is controlled by a fieldbus and a
timeout is detected.
3.29 Parameters: 40-** Special Settings
40-40 Fault Log: Ext. Reference
Range:
Function:
0 %
*
[-200 - 200 %]
40-41 Fault Log: Frequency
Range:
Function:
0 Hz
*
[0 - 6500 Hz]
40-42 Fault Log: Current
Range:
Function:
0 A
*
[0 - 10000 A]
40-43 Fault Log: Voltage
Range:
Function:
0 V
*
[0 - 6000 V]
40-44 Fault Log: DC Link Voltage
Range:
Function:
0 V
*
[0 - 10000 V]
40-45 Fault Log: Control Word
Range:
Function:
0
*
[0 - 65535 ]
40-46 Fault Log: Status Word
Range:
Function:
0
*
[0 - 65535 ]
3.29.1 40-5* Advanced Control Settings
Parameters for configuring the advanced motor control
settings.
40-50 Flux Sensorless Model Shift
Use this parameter to enable or disable the shifting between flux
model 1 and flux model 2 at low speed. See also
parameter 1-66 Min. Current at Low Speed
.
Option:
Function:
[0]
Off
[1]
On
40-51 Flux Sensorless Corr. Gain
Range:
Function:
Size related
*
[0.1 - 200.0 ]
3.30 Parameters: 42-** Safety Functions
The parameters in this parameter group are available when
a safety option is installed in the frequency converter. For
information about the safety-related parameters, see the
operating instructions for the safety options:
•
VLT
®
Safety Option MCB 150/151 Operating
Instructions
.
•
VLT
®
Safety Option MCB 152 Operating Instructions
.
42-37 Level 1 Password Buffer
Range:
Function:
Size related
*
[0 - 8 ]
42-87 Time Until Manual Test
Range:
Function:
8761 h
*
[0 - 8761 h]
3.31 Parameters: 43-** Unit Readouts
The parameters in this group provide readouts for
monitoring the operation of frequency converters in the
D–F enclosure sizes.
3.31.1 43-0* Component Status
This parameter group contains read-only information on
hardware components in the power section. All parameters
in this group are arrays:
Parameter Descriptions
Programming Guide
MG33MP02