4-19 Max Output Frequency
Range:
Function:
Size
related
*
[ 1 -
590
Hz]
NOTICE
This parameter cannot be adjusted
while the motor is running.
NOTICE
Maximum output frequency cannot
exceed 10% of the inverter switching
frequency (
Provides a final limit on the output frequency
for improved safety in applications where
overspeeding is to be avoided. This limit is
final in all configurations (independent of the
setting in
parameter 1-00 Configuration Mode
).
4-20 Torque Limit Factor Source
Option:
Function:
Select an analog input for scaling the
settings in
and
0–100% (or
inverse). The signal levels corresponding
to 0% and 100% are defined in the
analog input scaling, for example
parameter group 6-1* Analog Input 1
. This
parameter is only active when
parameter 1-00 Configuration Mode
is in
Speed Open Loop
or
Speed Closed Loop
.
[0]
*
No function
[2]
Analog in 53
[4]
Analog in 53 inv
[6]
Analog in 54
[8]
Analog in 54 inv
[10] Analog in X30-11
[12] Analog in X30-11
inv
[14] Analog in X30-12
[16] Analog in X30-12
inv
4-21 Speed Limit Factor Source
Option:
Function:
Select an analog input for scaling the
settings in
0–100% (or the other way
around). The signal levels corresponding
to 0% and 100% are defined in the
analog input scaling, for example
parameter group 6-1* Analog Input 1
. This
parameter is only active when
4-21 Speed Limit Factor Source
Option:
Function:
parameter 1-00 Configuration Mode
is in
[4] Torque Open Loop
.
[0]
*
No function
[2]
Analog in 53
[4]
Analog in 53 inv
[6]
Analog in 54
[8]
Analog in 54 inv
[10] Analog in X30-11
[12] Analog in X30-11
inv
[14] Analog in X30-12
[16] Analog in X30-12
inv
4-23 Brake Check Limit Factor Source
Select the input source for the function in
. If several frequency converters are carrying out a brake
check simultaneously, the resistance in the grid leads to a
voltage drop on the mains or DC-link and a false brake check
can occur. Use an external current sensor on every brake resistor.
If an application requires a 100% valid brake check, connect the
sensor to an analog input.
Option:
Function:
[0]
*
DC-link voltage
The frequency converter
performs the brake check by
monitoring the DC-link
voltage. The frequency
converter injects current in
the brake resistor which
lowers the DC-link voltage.
[1]
Analog Input 53
Select to use an external
current sensor for brake
monitoring.
[2]
Analog Input 54
Select to use an external
current sensor for brake
monitoring.
4-24 Brake Check Limit Factor
Range:
Function:
98
%
*
[0 -
100 %
]
Enter the limit factor that
uses when performing the brake check. The
frequency converter uses the limit factor
depending on the selection in
parameter 4-23 Brake Check Limit Factor Source
:
[0] DC-link voltage
- the frequency converter
applies the factor to the EEPROM data in the DC-
link.
[1] Analog Input 53
or
[2] Analog Input 54
- the
brake check fails if the input current on the analog
input is lower than the maximum input current
multiplied by the limit factor.
Parameter Descriptions