3.13.2 13-1* Comparators
Comparators are used for comparing continuous variables
(that is output frequency, output current, analog input, and
so on) to fixed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Illustration 3.54 Comparators
There are digital values that are compared to fixed time
values. See the explanation in
parameter 13-10 Comparator
Operand
. Comparators are evaluated once in each scan
interval. Use the result (true or false) directly. All
parameters in this parameter group are array parameters
with index 0–5. Select index 0 to program comparator 0,
select index 1 to program comparator 1, and so on.
13-10 Comparator Operand
Option:
Function:
Options
[1] Reference %
to
[31] Counter B
are variables which are compared based
on their values. Options
[50] FALSE
to
[186] Drive in auto mode
are digital values
(true/false) where the comparison is
based on the amount of time during
which they are set to true or false. See
parameter 13-11 Comparator Operator
Select the variable to be monitored by
the comparator.
[0]
DISABLED
The comparator is disabled.
[1]
Reference %
The resulting remote reference in
percent.
[2]
Feedback %
[RPM] or [Hz], as set in
parameter 0-02 Motor Speed Unit
[3]
Motor speed
[RPM] or [Hz], as set in
parameter 0-02 Motor Speed Unit
[4]
Motor Current
[5]
Motor torque
[6]
Motor power
[7]
Motor voltage
[8]
DC-link voltage
[9]
Motor Thermal
Value is in percent.
[10]
Drive thermal
Value is in percent.
[11]
Heat sink temp. Value is in percent.
[12]
Analog input
AI53
Value is in percent.
13-10 Comparator Operand
Option:
Function:
[13]
Analog input
AI54
Value is in percent.
[14]
Analog input
AIFB10
AIFB10 is internal 10 V supply.
[15]
Analog input
AIS24V
AIS24V is a 24 V switch mode power
supply.
[17]
Analog input
AICCT
Value is in [°]. AICCT is control card
temperature.
[18]
Pulse input FI29 Value is in percent.
[19]
Pulse input FI33 Value is in percent.
[20]
Alarm number
The number of registered alarms.
[21]
Warning
number
[22]
Analog input
x30 11
[23]
Analog input
x30 12
[30]
Counter A
[31]
Counter B
[32]
Process PID
Error
Value of the PID error
(
parameter 18-90 Process PID Error
[33]
Process PID
Output
Value of the PID output
(
parameter 18-91 Process PID Output
).
[34]
Analog Input
x48/2
[35]
Temp Input
x48/4
[36]
Temp Input
x48/7
[37]
Temp Input
x48/10
[38]
Actual Position
NOTICE
This option is only available for
software version 48.XX
[39]
Safe Opt. Speed
Error
[50]
FALSE
Use to enter the fixed value of false in
the comparator.
[51]
TRUE
Use to enter the fixed value of true in
the comparator.
[52]
Control ready
The control board receives supply
voltage.
[53]
Drive ready
The frequency converter is ready for
operation and applies a signal on the
control board.
[54]
Running
The motor runs.
[55]
Reversing
The output is active when the frequency
converter runs counterclockwise (the
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
170
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3