18-45 Analog Out X49/11
Range:
Function:
0
*
[0 - 30 ] Shows the actual value at output of terminal
X49/11 in V or mA. The value reflects the
selection in
parameter 36-60 Terminal X49/11
.
3.18.3 18-5* Active Alarms/Warnings
The parameters in this group show the numbers of
currently active alarms or warnings.
18-55 Active Alarm Numbers
Range:
Function:
0
*
[0 - 65535 ] This parameter contains an array of up to 20
alarms that are currently active. The value 0
means no alarm.
18-56 Active Warning Numbers
Range:
Function:
0
*
[0 - 65535 ] This parameter contains an array of up to 20
warnings that are currently active. The value 0
means no warning.
18-60 Digital Input 2
Range:
Function:
0
*
[0 - 65535 ] Shows the signal states from the active digital
inputs.
•
0 = No signal.
•
1 = Connected signal.
18-70 Mains Voltage
Range:
Function:
0 V
*
[0 - 1000 V]
Shows the mains line-to-line voltage.
18-71 Mains Frequency
Range:
Function:
0 Hz
*
[-100 - 100 Hz]
Shows the mains frequency.
18-72 Mains Imbalance
Range:
Function:
0 %
*
[0 - 100 %] Shows the maximum imbalance for the 3
mains line-to-line measurements.
18-75 Rectifier DC Volt.
Range:
Function:
0 V
*
[0 - 10000 V] Shows the DC voltage measured on the
rectifier module.
18-90 Process PID Error
Range:
Function:
0 %
*
[-200 - 200 %] Give the present error value used by the
process PID controller.
18-91 Process PID Output
Range:
Function:
0 %
*
[-200 - 200 %] Give the present raw output value from
the process PID controller.
18-92 Process PID Clamped Output
Range:
Function:
0 %
*
[-200 - 200 %] Give the present output value from the
process PID controller after the clamp
limits have been observed.
18-93 Process PID Gain Scaled Output
Range:
Function:
0 %
*
[-200 -
200 %]
Give the present output value from the
process PID controller after the clamp
limits have been observed, and the
resulting value has been gain scaled.
3.19 Parameters: 19-** Application
Parameters
Parameters in this group are available when VLT
®
Motion
Control Option MCO 305 is installed in the frequency
converter. For information about the option, see the
VLT
®
Motion Control Option MCO 305 Operating Instructions.
3.20 Parameters: 22-** Appl. Functions
22-00 External Interlock Delay
Range:
Function:
0 s
*
[0 - 600 s]
3.21 Parameters: 23-** Time-based
Functions
3.21.1 23-0* Timed Actions
Use timed actions for actions performed on a daily or
weekly basis, for example different references for working
hours/non-working hours. Up to 10 timed actions can be
programmed in the frequency converter. Select the timed
action number from the list when entering
parameter
group 23-** Time-based Functions
from the LCP.
Parameter 23-00 ON Time
and
parameter 23-04 Occurrence
then refer to the selected timed action number. Each
timed action is divided into an ON time and an OFF time,
in which 2 different actions may be performed.
Display lines 2 and 3 in the LCP show the status for timed
actions mode (
parameter 0-23 Display Line 2 Large
and
parameter 0-24 Display Line 3 Large
, setting
[1643] Timed
Actions Status
).
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
226
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02
3
3