Set-up
Set-up
Set-up
Set-up
PLC Fieldbus
Illustration 3.1 Edit Set-up
0-12 This Set-up Linked to
Option:
Function:
To enable conflict-free changes from 1 set-up to
another during operation, link set-ups
containing parameters which are
not changeable
during operation
. The link ensures synchronizing
of the
not changeable during operation
-
parameter values when moving from 1 set-up
to another during operation.
Not changeable
during operation
-parameters can be identified
by the label FALSE in the parameter lists in
.
Parameter 0-12 This Set-up Linked to
is used by
[9] Multi set-up
in
parameter 0-10 Active Set-up
.
Multi set-up is used to move from 1 set-up to
another during operation (that is while the
motor runs).
Example:
Use multi set-up to shift from set-up 1 to set-up
2 while the motor runs. Program in set-up 1
first, then ensure that set-up 1 and set-up 2 are
0-12 This Set-up Linked to
Option:
Function:
synchronized (or linked). Synchronization can be
performed in 2 ways:
1. Select the following options:
•
[2] Set-up 2
in
parameter 0-11 Edit Set-
up
.
•
parameter 0-12 This Set-up Linked to
to
[1] Set-up 1
.
This starts the linking (synchronizing) process.
130BP075.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[1]
Setup 1
Illustration 3.2 Set-up 1
OR
2. While still in set-up 1, copy set-up 1 to set-up
2. Then set
parameter 0-12 This Set-up Linked to
to
[2] Set-up 2
. This starts the linking process.
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
Illustration 3.3 Set-up 2
When completed,
parameter 0-13 Readout:
Linked Set-ups
reads {1,2} to indicate that all
not
changeable during operation
-parameters are now
the same in set-up 1 and set-up 2. If there are
changes to a
not changeable during operation
-
parameter, for example
parameter 1-30 Stator
Resistance (Rs)
, in set-up 2, they are also
changed automatically in set-up 1. A switch
between set-up 1 and set-up 2 during
operation is now possible.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
*
[0 -
255 ]
View a list of all the set-ups linked by
parameter 0-12 This Set-up Linked to
. The parameter
Parameter Descriptions
VLT
®
AutomationDrive FC 301/302
26
Danfoss A/S © 10/2018 All rights reserved.
MG33MP02