3-07 Maximum Position
Range:
Function:
100000
CustomRea-
doutUnit2
*
[-2147483648
- 2147483647
CustomRea-
doutUnit2]
NOTICE
This parameter is only
available with software
version 48.XX.
Enter the maximum position. This
parameter defines the position
range in linear and axis modes
(
).
Position range limits:
•
Linear:
Parameter 3-06 Minimum
Position
to
parameter 3-07 Maximum
Position
•
Rotary: 0–
parameter 3-07 Maximum
Position
The position limit function uses
this parameter
(
).
3-08 On Target Window
Range:
Function:
5 CustomRea-
doutUnit2
*
[0 -
2147483647
CustomRea-
doutUnit2]
NOTICE
This parameter is only
available with software
version 48.XX.
The frequency converter
considers the positioning
completed and sends the on
target signal when the actual
position is within
parameter 3-08 On Target
Window
for the duration of
and the actual speed is less
than
.
3-09 On Target Time
Range:
Function:
1 ms
*
[0 - 60000
ms]
NOTICE
This parameter is only available with
software version 48.XX.
Enter the time for evaluating the on
target window, see also
3.4.2 3-1* References
Select the preset references. Select
Preset ref. bit 0/1/2 [16],
[17], or [18]
for the corresponding digital inputs in
parameter group 5-1* Digital Inputs
.
3-10 Preset Reference
Array [8]
Range: 0-7
Range:
Function:
0 %
*
[-100 -
100 %]
Enter up to 8 different preset references (0–7) in
this parameter, using array programming. The
preset reference is stated as a percentage of the
value Ref
MAX
parameter 3-03 Maximum Reference
If a Ref
MIN
different from 0
parameter 3-02 Minimum Reference
) is
programmed, the preset reference is calculated
as a percentage of the full reference range, that
is on the basis of the difference between Ref
MAX
and Ref
MIN
. Afterwards, the value is added to
Ref
MIN
. When using preset references, select
preset reference bit 0/1/2 [16], [17] or [18] for the
corresponding digital inputs in
parameter group
5-1* Digital Inputs
.
[P 5-13=Preset ref. bit 0]
Preset
[P 5-14=Preset ref. bit 1]
[P 5-15=Preset ref. bit 2]
10101010
76543210
29
12 (+24V)
11001100
32
11110000
33
130BA149.10
Illustration 3.21 Preset Reference
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
77
3
3