16-52 Feedback[Unit]
Range:
Function:
0 Reference-
FeedbackUnit
*
[-999999.999 -
999999.999
ReferenceFeed-
backUnit]
View the feedback unit
resulting from the selection
of unit and scaling in
parameter 3-01 Reference/
Feedback Unit
parameter 3-02 Minimum
Reference
, and
parameter 3-03 Maximum
Reference
16-53 Digi Pot Reference
Range:
Function:
0
*
[-200 - 200 ] View the contribution of the digital potenti-
ometer to the actual reference.
16-57 Feedback [RPM]
Range:
Function:
0 RPM
*
[-30000 -
30000 RPM]
Readout parameter where the actual motor
RPM from the feedback source can be read
in both closed loop and open loop. The
feedback source is selected by
parameter 7-00 Speed PID Feedback Source
3.16.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[ 0 -
65535 ]
View the signal states from the active digital
inputs. Example: Input 18 corresponds to bit
number 5, 0 = no signal, 1 = connected signal. Bit
6 works in the opposite way, on = 0, off = 1 (Safe
Torque Off input).
Bit 0
Digital input terminal 33.
Bit 1
Digital input terminal 32.
Bit 2
Digital input terminal 29.
Bit 3
Digital input terminal 27.
Bit 4
Digital input terminal 19.
Bit 5
Digital input terminal 18.
Bit 6
Digital input terminal 37.
Bit 7
Digital input VLT
®
General Purpose
I/O MCB 101 terminal X30/4.
Bit 8
Digital input VLT
®
General Purpose
I/O MCB 101 terminal X30/3.
Bit 9
Digital input VLT
®
General Purpose
I/O MCB 101 terminal X30/2.
Bit 10–63
Reserved for future terminals.
Table 3.31 Active Digital Inputs
16-60 Digital Input
Range:
Function:
Illustration 3.68 Relay Settings
16-61 Terminal 53 Switch Setting
View the setting of input terminal 53.
Option:
Function:
[0]
*
Current
[1]
Voltage
16-62 Analog Input 53
Range:
Function:
0
*
[-20 - 20 ]
View the actual value at input 53.
16-63 Terminal 54 Switch Setting
View the setting of input terminal 54.
Option:
Function:
[0]
*
Current
[1]
Voltage
16-64 Analog Input 54
Range:
Function:
0
*
[-20 - 20 ]
View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range:
Function:
0
*
[0 - 30 ] View the actual value at output 42 in mA. The
value shown reflects the selection in
parameter 6-50 Terminal 42 Output
.
16-66 Digital Output [bin]
Range:
Function:
0
*
[0 - 15 ]
View the binary value of all digital outputs.
16-67 Freq. Input #29 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual frequency rate on terminal 29.
Parameter Descriptions
Programming Guide
MG33MP02
Danfoss A/S © 10/2018 All rights reserved.
213
3
3