![Balluff BVS ID-M1280 F1 Series Configuration Manual Download Page 296](http://html1.mh-extra.com/html/balluff/bvs-id-m1280-f1-series/bvs-id-m1280-f1-series_configuration-manual_3655213296.webp)
BVS ID-M1280xF1-xx-xxx
138
english
•
•
•
•
•
Vibration Alarm Threshold
Threshold value of the vibration for triggering an event. The comparison is performed for each axis and variable
with logical OR-link.
The hysteresis is fixed and is based on time (not on amplitude). If the vibration value exceeds the threshold value
for 50 ms, the alarm is activated.
Objective: debouncing and avoidance of shock values.
Unit: [mm/s]
Minimum value: 0,0
Maximum value: 1770,0
Vibration Alarm Status
The status flag is TRUE if the vibration exceeds the alarm threshold value.
0 = no alarm
255 = alarm
Events
Event
Code
Event Type
Event – Description – Remedy
Device Status
0x8CD1
(36049)
Warning
Vibration alarm
→
Check machine.
0 – Device is operating properly.
This event indicates that the measured vibration value (v-RMS) exceeds the specified threshold value. The
machine should be inspected since the vibration value is above the normal value. The status of the
BVS ID
itself
is OK, it is functioning properly.
The higher vibration is caused outside of the
BVS ID
. The primary goal is the detection of trends, changes to
the vibration alarm value (see figure above yellow line).
Summary of Contents for BVS ID-M1280 F1 Series
Page 1: ...deutsch Konfigurationsanleitung english Configuration Guide BVS ID M1280xF1 xx xxx...
Page 2: ...www balluff com...
Page 3: ...deutsch Konfigurationsanleitung BVS ID M1280xF1 xx xxx...
Page 4: ...www balluff com...
Page 41: ...BVS ID M1280xF1 xx xxx deutsch 39...
Page 96: ...BVS ID M1280xF1 xx xxx 94 deutsch Ablaufdiagramm Handshake mit Input Toggle...
Page 157: ...956115_AB DE E23 nderungen vorbehalten Ersetzt K22...
Page 158: ......
Page 159: ...english Configuration Guide BVS ID M1280xF1 xx xxx...
Page 160: ...www balluff com...
Page 197: ...BVS ID M1280xF1 xx xxx english 39...
Page 250: ...BVS ID M1280xF1 xx xxx 92 english Flowchart Handshake with Input Toggle...
Page 315: ...956115_AB EN E23 Subject to modification Replaces K22...