BVS ID-M1280xF1-xx-xxx
126
english
4.4.9.4 Voltage and Current Monitoring
Description
The voltage and current module send messages about over-current, short-circuit, wire breakage, over-voltage
and under-voltage. Over-voltage and under-voltage detection starts a timer. If the timer has expired and the
voltage level has not returned to the normal operating voltage threshold, the module sends out the messages.
The messages include device status, IO-Link events, process data and LED signaling
Mathematics/Algorithm
In SIO mode or in IO-Link mode the threshold for undervoltage is 17 V and for overvoltage is 31 V.
Process Data
Object ID
Name
Description
Direction
0x0016 (21) Overload / short-circuit pin 4
TRUE = overload or short-circuit detected at pin 4.
Input
0x0016 (22) Overload / short-circuit pin 2
TRUE = overload or short-circuit detected at pin 2.
Input
0x0017 (23) Undervoltage pin 1/3
TRUE = the voltage level at pin 1/3 is below the threshold
value.
Input
0x0018 (24) Overvoltage pin 1/3
TRUE = the voltage level at pin 1/3 is above the threshold
value.
Input
0x0019 (25) Cable break pin 4
TRUE = cable break detected at pin 4.
Input
0x001A
(26)
Cable break pin 2
TRUE = cable break detected at pin 2.
Input
0x0043 (67) Overload pin 4
TRUE = overload detected at pin 4.
Input
0x0044 (68) Overload pin 2
TRUE = overload detected at pin 2.
Input
Pin 2 and pin 4 can be the pins at the IO-Link port or at the I/O port.
ISDU
Name
Index
Subinde
x
Acces
s
Length
Data Type
Data
Storage
Default
Voltage Monitoring
Detection Time Duration
0x2200
(8704)
0
R/W
2 bytes
UINT16
Yes
10
Voltage Monitoring Detection Time Duration
This parameter is used to define how long the undervoltage or over-voltage must be present before it is
displayed. The unit is given in milliseconds. The values must be in the range between 10 and 1000, in
increments of 5 milliseconds. The default value is 10 milliseconds.
System Commands
Command Value
Device Action
0x81 (129)
Application Reset – Resets the Voltage Monitoring Detection Time Duration with ISDU-index 0x2200 to the
default value 10.
0x82 (130)
Reset Factory Settings – Resets the Voltage Monitoring Detection Time Duration with ISDU-index 0x2200
to the default value 10.
Summary of Contents for BVS ID-M1280 F1 Series
Page 1: ...deutsch Konfigurationsanleitung english Configuration Guide BVS ID M1280xF1 xx xxx...
Page 2: ...www balluff com...
Page 3: ...deutsch Konfigurationsanleitung BVS ID M1280xF1 xx xxx...
Page 4: ...www balluff com...
Page 41: ...BVS ID M1280xF1 xx xxx deutsch 39...
Page 96: ...BVS ID M1280xF1 xx xxx 94 deutsch Ablaufdiagramm Handshake mit Input Toggle...
Page 157: ...956115_AB DE E23 nderungen vorbehalten Ersetzt K22...
Page 158: ......
Page 159: ...english Configuration Guide BVS ID M1280xF1 xx xxx...
Page 160: ...www balluff com...
Page 197: ...BVS ID M1280xF1 xx xxx english 39...
Page 250: ...BVS ID M1280xF1 xx xxx 92 english Flowchart Handshake with Input Toggle...
Page 315: ...956115_AB EN E23 Subject to modification Replaces K22...