AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
26
AC90-T3-450T 1000A 2000A DCL-1000 ------
------
AC90-T3-500T 1000A 2000A DCL-1200 ------
------
AC90-T3-560T ------ 2000A
DCL-1200 ------
------
Note: For DC reactor, input filter, output filter and other components specification details and circuit mode, please refer
chapter 7 “peripheral equipments and options”.
Chart 3-9: Suggested mains fittings for 3-phase 380V machine
Control loop terminals
●
Control loop terminals array
Sort
Terminal
Name
Function definition
Passive
connection output
TA Normally-open
contact
Can set the action-object by programme.
Max contact capacity:3A/240VAC 5A/30VDC
TB Normally-closed
contact
TC
Common contact
State output
Y1
Collector open output 1
Can set the action-object by programme.
Max contact capacity:DC30V/50mA
Y2
Collector open output 2
Auxiliary
power supply
+24V
Auxiliary power
Max output: 24VDC/100mA.
COM
Auxiliary power output -
Multi-function
contact input
X1
Multi-function contact
input 1 (forward)
Build-in photoelectric converter can set the
action-object by programme.
Input condition: Max DC30V/8mA.
Note:
Factory setting is common-collector characteristic
input. If need common-emitter characteristic input,
Please remove the short connector b24V”and
“PLC”, then use the short connector to connect “PLC”
and “COM”.
X2
Multi-function contact
input 2 (reverse)
X3
Multi-function contact
input 3
(
forward jog
)
X4
Multi-function contact
input 4
(
reverse jog
)
X5
Multi-function contact
input 5
(
free stop
)
X6
Multi-function contact
input 6
(
fault reset
)