AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
125
9.11 Malfunction and protection parameters
FA.00
Protection functionselection 1
Setting range: 0000-0111
Factory set: 0001
LED “0”digit: ACC OC protection selection
0: Invalid
1: Valid
While inverter output frequency is over
[FA.15]
setting, inverter enters OC protection state, prolong ACC time
and not continue ACC until frequency back to
[FA.15]
setting.
LED“00”digit: DEC OC protection selection
While inverter output frequency is over
[FA.16]
setting, inverter enters OC protection state, prolong DEC time and not
continue DEC until frequency back to
[FA.16]
setting.
0: Invalid
1: Valid
LED“000”digit: current limit selection while running
While inverter output frequency is over
[FA.17]
setting, inverter enters current limit state, reduce output frequency
according to
[FA.18]
ACC/DEC time setting and not continue ACC according to
[FA.18]
ACC/DEC time setting until
frequency back to
[FA.17]
setting.
0: Invalid
1: Valid
LED“0000”digit: reserved
FA.01
Protection function selection 2
Setting range: 0000-3212
Factory set: 0001
LED “0”digi: DEC OV protection selection
0: Invalid
1: rating 1 OV protection
Stonger OV protection. Bus voltage wave is small while protection.
2: rating 2 OV protection
Stongest OV protection. Bus voltage wave is big while protection.
While it is valid and bus voltage is reach or over
[FA.05]
, inverter will stop DEC.
LED“00”digit: Protection selection for OV in ACC or constant speed
0: Invalid
1: Valid While bus voltage is reach or over
[FA.06]
, inverter will adjust frequency to protect. It is valid specially for
eccentric load