AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
38
●
Run command instructions
Four run command channels: 0: keyboard control, 1: terminal control,
2:RS485 communication control, 3: optional card. It can be set by F0.02.
Here we set F0.02=1(terminal control) as an example:
Chart 4-4: Run command instructions
It introducs terminal control two-wire 1, which is one kind of terminal control mode. For the other control modes, please
refer the chapter 9.
●
Frequency command instructions
There are many kinds of requency command instruction selections. Please refer to chapter 9 for details. Here we set
F0.03=1(keyboard potentionmeter give frequency) as an example:
Chart 4-5: Frequency command instructions
●
Start-up mode selections
Three start-up modes: 0: direct start-up, 1: braking firstly, then start by start-up frequency, 2: speed track and start-up.
Here we set Fa.00=2(speed track and start-up) as an example:
Chart 4-6: Start-up mode selections
●
Stop mode selections
Three stop modes: 0: deceleration stop, 1: free stop, 2: all range DC braking stop. Here we set F1.07=1(all range DC
braking stop) as an example:
Chart 4-7: Stop mode selections