AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
97
F3.08
VS2 upper limit
corresponding setting
Setting range: 0.00-100.00%
Factory set: 100.00%
F3.09
VS2 filter time
Setting range: 0.00-10.00s Factory
set: 0.10s
F3.10
AS Lowest limit
Setting range: 0.00-20.00mA
Factory set: 4.00mA
F3.11
AS Lowest limit
corresponding setting
Setting range: 0.00-100.00%
Factory set: 0.00%
F3.12
AS upper limit
Setting range: 0.00-20.00mA
Factory set: 20.00mA
F3.13
AS upper limit
corresponding setting
Setting range: 0.00-100.00%
Factory set: 100.00%
F3.14
AS filter time
Setting range: 0.00-10.00s Factory
set: 0.10s
See VS1 explain.
F3.15-F3.21 Reserved
Used for setting inverter monitor corresponding to multifunction terminal
(AO1)
,
(AO2)
output signal.
(AO1)
output signal is voltage signal 0-10V.
(AO2)
output signal is decided by
[F3.26]
.
Setting
monitor
Function
AO min output
AO max output
0 Set
frequency
Corresponding to current
give frequency
Min output corresponding
to 0.00Hz
Max output corresponding to
max frequency
1
running
frequency
Corresponding to current
output frequency
Min output corresponding
to 0.00Hz
Max output corresponding to
max frequency
2 Output
current
Corresponding to current
output current
Min output corresponding
to 0.00A
Max output corresponding to
2 times of rated current
3 Input
voltage
Corresponding to voltage
input voltage
Min output corresponding
to 0V
Max output corresponding to
2 times of rated voltage
4 Output
voltage
Corresponding to voltage
output voltage
Min output corresponding
to 0V
Max output corresponding to
rated voltage
5 Run
speed
Corresponding to machine
speed which corresponding
to the inverter outout
Min output is
corresponding to 0RPM
Max output is corresponding
to speed which is
corresponding to max
6 Set
torque Corresponding to current
inverter give torque
Min output corresponding
to 0.00% torque
Max output corresponding to
200% torque
7 Output
torque
Corresponding to current
output torque
Min output corresponding
to 0.00% torque
Max output corresponding to
200% torque
8 PID
give
Corresponding to current
PID give
Min output corresponding
to 0.00% PID give
Max output corresponding to
100% PID give
9 PID
feedback
Corresponding to current
PID feedback
Min output corresponding
to 0.00% PID feedback
Max output corresponding to
100% PID feedback
10 Set
tension
Corresponding to current
max tension setting of
Min output corresponding
to 0 power
Max output corresponding to
rated output power
11 Bus
voltage
Corresponding to current
input voltage
Min output corresponding
to 0V
Max output corresponding to
2 times rated DC voltage2
F3.22
A01 output selections
Setting range: 0-17
Factory set: 0
F3.23
A02 output selection
Factory set:1