AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
83
Frequency
Start ACC rate of S
curve(F1.14)set as 100%
Aim frequency
Start DEC rate of S
curve(F1.15)set as 100%
Start DEC rate of S
curve(F1.15)set as 20%
DEC time
Time
ACC time
start
frequency
Start ACC rate of S
curve(F1.14)set as 20%
ACC/DEC curve
F1.16-F1.17 Reserved
F1.18
ACC time 2
Setting range: 0.00-650.00s
Factory set: 10.00s
F1.19
DEC time 2
Setting range: 0.00-650.00s
Factory set: 10.00s
F1.20
ACC time 3
Setting range: 0.00-650.00s
Factory set: 10.00s
F1.21
DEC time 3
Setting range: 0.00-650.00s
Factory set: 10.00s
F1.22
ACC time 4
Setting range: 0.00-650.00s
Factory set: 10.00s
F1.23
DEC time 4
Setting range: 0.00-650.00s
Factory set: 10.00s
ACC time 2/3/4:
When
[F1.13]
LED“0”digit is 0, it means the time need for output frequency ACC from 0.00Hz to max
frequency
[F0.09]
. When
[F1.13]
LED“0”digit is 1, it means the time need for output frequency ACC from 0.00Hz to
50.00Hz. Details refer to
[F1.13]
.
DEC time 2/3/4:
When
[F1.13]
LED “0”digit is 0, it means the time need for output frequency DEC from max frequency
[F0.09]
to 0.00Hz. When
[F1.13]
LED “0”digit is 1, it means the time need for output frequency DEC from 50.00Hz to
0.00Hz.
ACC/DEC time details refer to
[FC.31-FC.45]
.
JOG ACC/DEC time is set by
[F1.33, F1.34]
ACC/DEC time table:
Terminal 2
Terminal 1
ACC/DEC time
OFF OFF
ACC/DEC time 1
OFF ON
ACC/DEC time 2
ON OFF
ACC/DEC time 3
ON ON
ACC/DEC time 4
If any unclear, please see FC parameter group multi steps time order fig.
F1.24
Emergency stop DEC time
Setting range: 0.01-650.00s
Factory set: 10.00s
Same as ACC/DEC time definition.
Emergency stop can be take effect by emergency stop terminal; details refer to
[F2.00-F2.07]
. While terminal control
two line run, whether carry out the orginal run order is decided by
[2.13]
LED “00” digit. Details refer to
[F2.13]
.