AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
86
9.3 Quantum digital terminal functions
F2.00
Multifunction input terminal 1(X1)
Setting range: 0-57
Factory set:1
F2.01
Multifunction input terminal 2(X2)
Factory set:2
F2.02
Multifunction input terminal 3(X3)
Factory set:4
F2.03
Multifunction input terminal 4(X4)
Factory set:5
F2.04
Multifunction input terminal 5(X5)
Factory set:6
F2.05
Multifunction input terminal 6(X6)
Factory set:8
F2.06
Multifunction input terminal 7(X7)
Factory set:56
F2.07
Multifunction input terminal 8(X8)
Factory set:57
Multifunction terminal (X1-X8) function can be defined by
[F2.00-F2.07]
. And trait and filter time can be defined by
[
F2.08-F2.11]
. Setting and function table:
setting
setting
setting
setting
0
No function( can choose again)
29
PID give switch 2
1 FWD
30
PID give switch 3
2 REV
31 PLC
pause
3
3 line run control(Xi)
32 PLC
restart
4 FWD
JOG
33
Swing frequency in
5 REV
JOG
34
Swing frequency pause
6 Free
stop
35
Swing frequency seset
7 Emergency
stop
36
Frequency channel switch terminal 1
8 Fault
reset
37
Frequency channel switch terminal 2
9 Out
fault
input
38
Frequency channel switch terminal 3
10 Frequency
(UP)
39
Frequency channel switch terminal 4
11 Freuqncy
(DW)
40
Timer touch terminal
12
(UP/DW clear )
41 Timer
clear
terminal
13 Reserved
42
Counter clock input terminal
14 Reserved
43 Counter
clear
terminal
15
Multi steps terminal 1
44
DC brake order
16
Multi steps terminal 2
45 Pre-excitation
order
terminal
17
Multi steps terminal 3
46 Reserved
18
Multi steps terminal 4
47 Start magnetic particle clutch function
19
ACC/DEC time selection terminal 1
48 PID parameter switch terminal 1
20
ACC/DEC time selection terminal 2
49 PID parameter switch terminal 2
21
ACC/DEC pause
50
Initial roll diameter setting terminal 1
22
PID control cancel
51
Initial roll diameter setting terminal 2
23
PID control pause
52
Linear speed selection terminal
24
PID trait switch
53
Material thickness selection terminal
25
PID give switch 1
54
Full roll diameter selection terminal
26
PID give switch 2
55 Empty to full roll time selection terminal
27
PID give switch 3
56
Roll diameter reset terminal
28
PID give switch 1
57
Roll diameter calculation pause
0: No function
This terminal invalid.
1: FWD
While run order is given by terminal, and
[F2.12]
is set as 2 lines 1, and terminal is valid, inverter will FWD.
Other control mode refers to
[F2.12]
.
2: REV
While run oder is given by terminal, and
[F2.12]
is set as 2 lines 1, and terminal is valid, inverter will REV. Other
control mode refers to
[F2.12]
.
3: 3 lines run control (Xi)
While run oder is given by terminal, and
[F2.12]
is set as 3 lines 1/2, it is 3 lines run control
(Xi). Details refer to
[F2.12]
.
4: FWD JOG