AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
107
9.8 Torque control parameter
F7.00
Torque give source
selection
Setting range: 0000-0577
Factory set: 0000
It used to select channel for torque given while torque control.
LED “0” digit: Main channel selection
0: Keyboard number given torque
[F7.01]
keyboard number give frequency give and modify main torque
1: Keyboard potentiometer given
2: VS1
3: VS2
4: AS
5: PUL
6: RS485 communication give
7: Tension control give
LED “00” digit: Second channel selection
0: Keyboard number given torque
[F7.01]
keyboard number give frequency give and modify main torque
1: Keyboard potentiometer given
2: VS1
3: VS2
4: AS
5: PUL
6: RS485 communication gives
7: Tension control gives
LED “000” digit: Main channel add second channel mode
0: MainX
[F7.02]
Main channel is valid, Main channel giving value is main channel giving value multiply torque give
main channel gain
[F7.02]
1: Second
×
[F7.03]
Second channel is valid, Second channel giving value is second channel giving value multiply
torque give second channel gain
[F7.03]
2: MainX
[F7.02]
+
SecondX
[F7.03]
The result of main channel giving value multiply torque give main channel gain
[F7.02]
add the result of second channel giving value multiply torque give second channel gain
[F7.03]
. Then sum is
the output torque of the inverter.
3: Main X
[F7.02]
-
Second X
[F7.03]
The result of main channel giving value multiply torque give main channel
gain
[F7.02]
minus the result of second channel giving value multiply torque give second channel gain
[F7.03]
. Then
the result is the output torque of the inverter.
4: MAX{main X
[F7.02]
,second X
[F7.03]
} The bigger one of the result of main channel giving value multiply torque
give main channel gain
[F7.02]
and the result of second channel giving value multiply torque give second channel
gain
[F7.03]
is the output torque of the inverter.
5: MIN {main X
[F7.02]
,second X
[F7.03]
} The smaller one of the result of main channel giving value multiply torque
give main channel gain
[F7.02]
and the result of second channel giving value multiply torque give second channel
gain
[F7.03]
is the output torque of the inverter.
LED “0000” digit: Reserved
F7.01
Keyboard number give
torque
Setting range: 0%-200.0%
Factory set: 100.0%
Set torque given value by keyboard. While
[F4.04]
LED “0” digit is 2, the parameter can be modified by UP/DW key.
Whether save modification is decided by
[F4.04]
LED “00” digit setting. It can adjust torque given value.