AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
78
frequency, free stop frequency, stop DC brake start frequency, jump frequency and so on. Max
frequency, upper limitation and lowest limitation relationship as below:
F0.14
ACC time 1
Setting range: 0.01-650.00s
Factory set: Accord model
F0.15
DEC time 1
Setting range: 0.01-650.00s
Factory set: Accord model
ACC time 1:
When
[F1.13]
LED “0”digit is 0, it means the time needed for output frequency accelerate from 0.00Hz to
max frequency
[F0.09]
. When
[F1.13]
LED “0”digit is 1, it means the time needed for output frequency accelerate from
0.00Hz to 50.00Hz. Details refer to
[F1.13]
.
DEC time 1:
When
[F1.13]
LED “0”digit is 0, it means the time needed for output frequency decelerate from max
frequency
[F0.09]
to 0.00Hz. When
[F1.13]
LED “0”digit is 1, it means the time needed for output frequency decelerate
from 50Hz to 0.00Hz. Details refer to
[F1.13]
.
This frequency inverter can set 4 kinds of ACC/DEC time max. If need to select other ACC/DEC time group, it must to
select by control terminal. Details refer to
[F2.00-F2.07]
and
[F1.18-F1.23]
.
ACC time is only valid for normal speed up process, not including start per-excite, start DC brake time and start
frequency hold time. DEC time is only valid for normal speed doen process, not including stop DC brake time.
During process running, ACC/DEC time 1 is defined as first kind of ACC/DEC time. The other 3 kinds of ACC/DEC time
details refer to
[F1.18-F1.23]
please.
JOG ACC/DEC time set by
[F1.33, F1.34]
alone.