AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
173
Fb.10
Differential coefficient
D1
0.00-10.00s 0.00s
●
135 0xB0A
Fb.11 Sample
cycle
0.01-100.00s
0.10s
●
136 0xB0B
Fb.12
PID control deviation
limitation
0.0-100.0% 0.0%
●
136 0xB0C
Fb.13 Reserved
0.0-100.0%
136
0xB0D
Fb.14
Detection time while
feedback wire break
0.0-6500.0s 1.0s
●
136 0xB0E
Fb.15
Action selections
while feedback wire
break
0: Go on PID operation without alarm
1: Stop and alarm malfunction
2: Go on PID operation and output
alarm signal
3: Run at the current frequency and
output alarm signal
0
●
136 0xB0F
Fb.16
Wire break alarm
upper limit
0.0-100.0% 100.0%
●
136 0xB10
Fb.17
Wire break alarm
lower limit
0.0-100.0% 0.0%
●
136 0xB11
Fb.18
Constant pressure
water supply sleep
system selection
0: Invalid
1: Valid
0
●
137 0xB12
Fb.19 Start-up
threshold
0.0-100.0%
0.0%
●
137 0xB13
Fb.20 Dormancy
threshold 0.0-100.0%
0.900
●
137 0xB14
Fb.21
Dormancy sense
DEC time
0-6500.0s 30.0s
●
137 0xB15
Fb.22
Stop sense low bit
hold frequency
0-20.00Hz 10.00Hz
●
137 0xB16
Multi-step, PLC function and swing frequency parameters
NO.
Function description
Range of settings and definition
Factory
setting
Attribute
Reference
page
Communica
tion add
FC.00
PLC Step 1
0.00-320.00Hz
10.00Hz
●
137 0xC00
FC.01
PLC Step 2
0.00-320.00Hz
20.00Hz
●
137 0xC01
FC.02
PLC Step 3
0.00-320.00Hz
30.00Hz
●
137 0xC02
FC.03
PLC Step 4
0.00-320.00Hz
40.00Hz
●
137 0xC03
FC.04
PLC Step 5
0.00-320.00Hz
50.00Hz
●
137 0xC04
FC.05
PLC Step 6
0.00-320.00Hz
40.00Hz
●
137 0xC05
FC.06
PLC Step 7
0.00-320.00Hz
30.00Hz
●
137 0xC06
FC.07
PLC Step 8
0.00-320.00Hz
20.00Hz
●
137 0xC07
FC.08
PLC Step 9
0.00-320.00Hz
10.00Hz
●
137 0xC08
FC.09
PLC Step 10
0.00-320.00Hz
20..00.H
●
137 0xC09
FC.10
PLC Step 11
0.00-320.00Hz
30.00Hz
●
137 0xC0A
FC.11
PLC Step 12
0.00-320.00Hz
40.00Hz
●
137 0xC0B
FC.12
PLC Step 13
0.00-320.00Hz
50.00Hz
●
137 0xC0C