AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
158
F4.16 LCD
language
LED “0” digit: LED display language
0: Chinese
1: English
LED“00” digit: output frequency
selection
0: Aim frequency
1: Actual frequency
LED“000”digit: machine speed display
selection
0: Aim speed
1: Actual speed
LED“0000” digit: reserved
0000
●
102 0x410
Motor parameters
NO.
Function description
Range of settings and definition
Factory
setting
Attribute
Referen
ce page
Communicati
on add
F5.00 Reserved
〇
103 0x500
F5.01
Number of motor
poles
2-48 4
〇
103 0x501
F5.02
Motor rated power
0.4-1000.0KW
Accord
model
〇
103 0x502
F5.03
Motor rated
frequency
0.01Hz-max frequency
Accord
model
〇
103 0x503
F5.04
Motor rated speed
0-65000rpm
Accord
model
〇
103 0x504
F5.05
Motor rated voltage
0-1500V
Accord
model
〇
103 0x505
F5.06
Motor rated current
0.1-2000.0A
Accord
model
〇
103 0x506
F5.07
Motor no-load current
0.01-650.00A
Accord
model
●
103 0x507
F5.08
Motor stator
resistance
0.001-65.000
Accord
model
●
103 0x508
F5.09
Motor rotor resistance
0.001-65.000
Accord
model
●
103 0x509
F5.10
Motor stator & rotor
inductance
0.1-6500.0mH
Accord
model
●
103 0x50A
F5.11
Motor stator & rotor
mutual inductance
0.1-6500.0mH
Accord
model
●
103 0x50C
F5.12
Motor parameters
self-adjustment
selections
0: No operation
1: Rotary type self-study
2: Resting type self-study
0
〇
103
0x50D
F5.13 Reserved
104
0x50E
F5.14 Reserved
104
0x50F