AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
168
F9.47
Empty to full roll time 2
0-65000s
7200
●
124
0x92F
F9.48 Current
time
0-65000s
*
●
124
0x930
F9.49
Reserved
124
0x931
F9.50
Reserved
124
0x932
F9.51
Reserved
124
0x933
Malfunction and protection parameters
NO.
Function description
Range of settings and definition
Factory
setting
Attribute
Reference
page
Communica
tion add
FA.00
Protection function
selection 1
LED “0”digit: ACC over-current
protection selection
0: Invalid
1: Valid
LED“00”digit: DEC over-current
protection selection
0: Invalid
1: Valid
LED“000”digit: current limit selection
while running
0: Invalid
1: Valid
LED“0000”digit: reserved
0001
●
125 0xA00
FA.01
Protection function
selection 2
LED“0”digit:DEC over-voltage
protection selection
0: Invalid
1: rating 1 over-voltage protection
2: rating 2 over-voltage protection
LED“00”digit: RUN over-voltage
protection selection
0: Invalid
1: Valid
LED“000”digit: inverter over-load
action selection
0: emergency stop output and alarm
1: emergency stop and alarm
2: limit current and run
LED “0000” digit: motor over-load act
0: emergency stop output and alarm
1: emergency stop and alarm
2: limit current and run
3: motor over-load protection off
0001
●
125 0xA01