![Veichi AC90 Скачать руководство пользователя страница 174](http://html1.mh-extra.com/html/veichi/ac90/ac90_manual_3940545174.webp)
AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL BASIC OPERATION AND TRIAL RUN
169
FA.02
Protection function
selection 3
LED “0”digit: inverter OH protection
selection
0: emergency stop output and alarm
1: emergency stop and alarm
2: limit current and run
LED“00”digit: input phase lack
protection selection
0: Invalid
1: Valid
LED“000”digit: output phase lack
protection selection
0: Invalid
1: Valid
LED“0000”digit: reserved
0110
●
126 0xA02
FA.03
Protection function
selection 4
LED “0”digit: SC protection selection
0: Invalid
1: Valid
LED“00”digit: OC protection selection
0: Invalid
1: Valid
LED“000”digit: reserved
LED“0000”digit: reserved
0000
●
127 0xA03
FA.04 Fan
control
0: Fan runs after electrifying
1: Fan stop related to temperature
and work while running
2: Fan stop while machine stop and
run related to temperature
1
●
127 0xA04
FA.05
DEC over-voltage
inhibition point
110-150% 120%
●
127 0xA05
FA.06
Running over-voltage
inhibition point
100-150% 115%
●
127 0xA06
FA.07
OV protection max
frequency add
0-50.00Hz 2.00Hz
●
127 0xA07
FA.08
Energy braking action
voltage
115.0%-140.0% 120.0%
●
128 0xA08
FA.09 Reserved
●
128 0xA09
FA.10
Bus under-voltage
protection
50.0%-100.0% 60.0%
●
128 0xA0A
FA.11
Speed fall act voltage at
sudden power down
0-200% 20%
●
128 0xA0B
FA.12
Main circuit aim voltage
at sudden power down
0%-200% 90%
●
128 0xA0C
FA.13
Speed fall gain at
sudden power down
0.01-10.00 2.00
●
128 0xA0D