AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
90
time 2 coming ture. Details see
[F9.46-F9.47]
.
56: Roll diameter reset terminal
In diameter calculation, set
[F9.18]
as “0” (roll diameter manual reset) and this
parameter is valid, inverter will back the roll diameter to initial value.
57: Roll diameter calculation pause
In diameter calculation, while this parameter is valid, inverter will stop roll
diameter calculation.
F2.08
X1-X4 terminal trait selection
Setting range: 0000-1111
Factory set: 0000
F2.09
X1-X4 input terminal filer time
Setting range: 0.000-60.000s
Factory set: 0.010s
X1-X4 terminal trait selections
LED "0”digit: X1 terminal
0: On valid
1: Off valid
LED“00”digit: X2 terminal
0: On valid
1: Off valid
LED “000”digit: X3 termina
l
0: On valid
1: Off valid
LED“0000”digit: X4terminal
0: On valid
1: Off valid
X1-X4 input terminal filer time:
When input terminal state changes, only if changed state keeps after filter time setting,
it is considered as valid terminal state change. Otherwise, it keeps last state to effectively avoid misact caused by
disturbance.
F2.10
X5-X8 terminal trait selection
Setting range: 0000-1111
Factory set: 0000
F2.11
X5-X8 input terminal filer time
Setting range: 0.000-60.000s
Factory set: 0.010s
Same as F2.08 and F2.09.
F2.12
Terminal control mode
Setting range: 0-3 Factory
set: 0
0:2-line 1
Run and direction in 1.Factory set is X1(FWD), X2(REV) terminals decide motor forward or reverse.
frequency inverter
FWD order(run while close)
REV order(run while close)
common input port
K1
K2 run order
0
1
0
1
0
0
1
1
stop
FWD
REV
COM
K1
K2
X1
X2
0: 2-line 1
COM