AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
99
F3.26
AO2 signal selection
Setting range: 0-3
Factory set: 0
0: 0-10V
1: 4.00-20.00mA
2: 0.00-20.00mA
3: FM Frequency pulse output output lowest limit is decided by
[F3.29]
, upper limit is set by
[F3.30]
.
Note: After output mode is selected by paremeter. J1, J2, J3 ON/OFF mode need to select according the
following ways:
1. If pulse output, J1 ON, J2, J3 OFF.
2. If 0.00-20.00mA or 4.00-20.00mA output, J2 ON, J1, J3 OFF.
3. If0-10V output, J1 ON, J2, J3 OFF.
Factory setting is 0-10V output for both hardware and software. If need change, please change both hardware
and software.
Switch terminal
Selection
position
cutline
function
J1
0.0-50kHz frequency output
J2
0-20mA current output
4-20mA current output
J3
0-10V voltage output
Same as AO1 setting.
F3.29
A02FM frequency output Lowest
limit
Setting range: 0.00-50.00kHz
Factory set: 0.20kHz
F3.30
A02FM frequency output upper
limit
Setting range: 0.00-50.00kHz
Factory set: 50.00kHz
While AO2 is set as FM frequency pulse output, it is lower limit and upper limit of the signal.
F3.27
A02 output gain
Setting range: 25.0-200.0%
Factory set: 100.0%
F3.28
A02 output signal bias
Setting range: -10.0-10.0%
Factory set: 0.0%