AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
139
ON
ON
ON
ON
ON
ON
ON
ON
1X
2X
3X
4X
ON
5X
7X
ON
ON
8X
ON
ON
9X
10X
11X
ON
12X
ON
13X
ON
14X
15X
ON
6X
frequency
time
multi steps terminal 4(X6)
multi steps terminal 3(X5)
multi steps terminal 2(X4)
multi steps terminal 1(X3)
REV(X3)
FWD(X3)
MULTI STEP TIME ORDER
FC.15
PLC run mode selections
Setting range: 0000-2212 Factory
set: 0000
LED “0” digit: cycle mode
0: Stop after single cycle
While receiving order, inverter run from the first step, time unit is set by
[FC.15]
LED “00”
digit. Running time is set by
[FC.16-FC.30]
. Running direction and ACC/DEC time is selected by
[FC.31-FC.45]
. Turn to
next step while run time is over, run time, direction, ACC/DEC time of every step can be set separately. Inverter output 0
Hz while finished 15 steps running. If one step running time is 0, it will skip this step.
1: Continuous cycles
Inverter not stop and runs at the latest speed while finished 15 steps running. Time unit is set by
[FC.15]
LED “00” digit. Run time is set by
[FC.16-FC.30]
. Run direction and ACC/DEC time is selected by
[FC.31-FC.45]
.
2: Keep final value after single cycle
Inverter back to 1
st
step while finished 15 steps running. Time unit is set by
[FC.15]
LED “00” digit. Run time is set by
[FC.16-FC.30]
. Run direction and ACC/DEC time is selected by
[FC.31-FC.45]