AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
108
F7.02
Main torque give channel gain
Setting range:0-500.0%
Factory set: 100.0%
F7.03
Second torque give channel gain
Setting range:0-500.0%
Factory set: 100.0%
Main torque give channel gain:
It is used to magnify or reduce the main channel torque by ratio.
Second torque give channel gain:
It is used to magnify or reduce the second channel torque by ratio.
F7.04 Reserved
F7.05
Output torque upper limit set
selection
Setting range: 0-6
Factory set: 0
Output torque upper limit set selection:
Select the giving source of the output torque upper limit.
0: Keyboard No give
Output torque upper limit set by
[F7.06]
; Max setting is smaller or equal to
[F7.06]
,
Smallest setting is bigger or equal to
[F7.07]
.
1: Keyboard potentiometer gives
2:VS1 give
3: VS2 give
4: AS give
5: PUL give
6: RS485 give
F7.06
Output torque upper
limit
Setting range: Lowest limit of output torque - max
output torque
Factory set:120.0%
F7.07
Output torque lowest
limit
Setting range: 0.0- upper limit of output torque
Factory set:1.0%
F7.08- F7.09
Reserved
F7.10
Zero speed value
Setting range: 0.00
~
50.00Hz
Factory set:1.00Hz
F7.11
Zero speed torque
gain
Setting range: 0.0
~
500.0%
Factory set:100.0%
Zero speed value:
It is recognited as zero speed working state while frequency inverter frequency is lower than [F7.10]
Zero speed torque gain:
It is output torque while frequency inverter is zero speed woring. It is mainly used for keeping
certain tension at zero speed. This value take give torque as base, totally corresponding to torque give value.
Calculation formula:
Torque at zero speed=give torque*zero speed torque gain
Use this value to set output torque at zero speed and running state separately to meet requirement
F7.12 Torque
ACC
time
Setting range: 0.00-100.00s
Factory set: 0.5s
F7.13 Torque
DEC
time
Setting range: 0.00-100.00s
Factory set: 0.5s
Torque ACC time:
Time of output torque from 0.0% up to 200.0% while torque control.
Torque DEC time:
Time of output torque from 200.0% down to 0.0% while torque control.