AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
82
frequency and stop work.
For inverter with build in braking unit (under than AC90-T3-018T, braking resistance (optional) can be used. When DC
bus voltage is over
[FA.08]
energy braking act voltage, inverter begins to carry out the energy braking act.
For inverter without build in braking unit (upper than AC90-T3-022T), braking unit and braking resistance can be
selected. It is mainly used for occasion that need quick braking while stop.
1: Free stop
Inverter stop output while receiving the stop order. Usually, it cooperates with exterior machine hold brake.
F1.08
Initial frequency of stop DC
braking
Setting range: 0.00-50.00Hz
Factory set: 0.00Hz
F1.09
Stop DC braking current
Setting range: 0.0-150.0% Factory
set: 0.0%
F1.10
Waiting time of stop DC
braking
Setting range: 0.0-60.0s
Factory set: 0.0s
F1.11
Stop DC braking duration
Setting range: 0.0-60.0s Factory
set: 0.0s
Initial frequency of stop DC braking:
While inverter DEC to this frequency, it will stop output and start DC braking.
Stop DC braking current:
It is the current that inverter give motor while DC braking. It is based on the output rated
current of the inverter. DC braking can afford 0 speed torque. It is uaually used for improve stop accuracy and quick
stop. It can’t be used for DEC braking for normal running.
Waiting time of stop DC braking:
It is the time for waitting to DC braking while inverter DEC to initial frequency of stop
DC braking and stop output.
Stop DC braking duration:
It is DC braking current holding time after stop. It is no DC braking process while braking
time is 0.0s.
F1.12 Reserved
F1.13
ACC/DEC mode selections
Setting range: 0000-0011 Factory
set: 0000
F1.14
Start ACC rate of S curve
Setting range: 20.0%-100.0%
Factory set: 50.0%
F1.15
Start DEC rate of S curve
Setting range: 20.0%-100.0%
Factory set: 50.0%
ACC/DEC mode selections
LED “0” digit: ACC/DEC time base
0: max frequency
Base is max frequency
[F0.09].
1: fixed frequency
Base is 50.00Hz.
LED “00” digit: ACC/DEC mode
0: Beeline
Suitable for general used load.
1: S Curve
Suitable for load need reduce noise, vibration, impact or load need descend torque for low frequency and
ACC short time for high frequency. If over current or over load while start, please increase
[F1.14]
setting.
LED “000” digit: reserved
LED “0000” digit: reserved
Start ACC rate of S curve:
It is the rate while start ACC. The smaller the rate is, the ACC S surve is sharper. Othwise,
The bigger the rate is, the ACC S surve is more like a beeline. If you want it ACC more smoothly, you can reduce the
rate and prolong ACC time.
Start DEC rate of S curve:
It is the rate while start DEC. The smaller the rate is, the DEC S surve is sharper. Othwise,
The bigger the rate is, the ACC S surve is more like a beeline. If you want it DEC more smoothly, you can reduce the
rate and prolong DEC time.