AC90 TENSION CONTROL FREQUENCY INVERTER MANUAL
Function Parameter specifications
88
ACC/DEC time selection terminal 1 is defaulted as valid while not set paremeter and terminal invalid. Details see
[F1.18-F1.23]
.
21: ACC/DEC pause
In ACC/DEC process, if it is valid, inverter stops ACC/DEC and keeps the speed. It is only valid
while inverter is running. It is invalid for DEC stop.
ON
ON
ON
ACC/DEC pause
pause
pause
ACC/DEC pause
give frequency
output frequency
run order
22: PID control cancel
While
[F0.03]
is set as 8 and this terminal is valid, it can make PID function be invalid. Main
frequency given channel gives 0.00Hz. While this terminal is invalid, PID re-count frequency given of main channel.
23: PID control pauses
While PID given and this terminal is valid, it can make PID adjustment be invalid and keep
frequency not change. PID re-counts frequency given of main channel.
24: PID trait switch
While
[F0.03]
is set as 8 and this terminal is valid,
[Fb.05]
LED “0” digit-trait setting will be
changed. PID output trait back to
[Fb.05]
LED “0” digit-trait setting.
25: PID given switch 1
26: PID given switch 2
27: PID given switch 3
While PID controller give signal source
[Fb.00]
is set as 8, give signal source channel can be switched by this group of
terminals. Details see
[Fb.00]
.
28: PID given switch 1
29: PID given switch 2
30: PID given switch 3
While PID controller feedback signal source
[Fb.02]
is set as 8, feedback signal source channel can be switched by this
group of terminals. Details refer to
[Fb.02]
.
31: PLC pause
While
[F0.03]
is 9, this valid signal can make PLC pause and inverter output 0.00Hz. Inverer go on as
before while this signal disappears. See parameter details of multi steps and FC group of PLC.
32: PLC restart
While
[F0.03]
is 9, this valid signal can make PLC start from the 1
st
step again at stop state or running.
See parameter details of multi steps and FC group of PLC.
33: Swing frequency in
Under swing frequency control, while set as manual swing frequency in and this terminal is
valid, swing frequency function is valid. And inverter begins swing frequency running. Details see
[FC.48-FC.54]
.
34: Swing frequency pause
Under swing frequency control, while this terminal is valid, inverter keeps frequency not
change and recover to swing frequency run after terminal order is cancelled. Details see
[FC.48-FC.54]
.
35: Swing frequency seset
Under swing frequency control, while this terminal is valid, inverter back to center
frequency and recover to swing frequency run after terminal order is cancelled. Details see
[FC.48-FC.54]
.
36: Frequency channel switch terminal 1
37: Frequency channel switch terminal 2
38: Frequency channel switch terminal 3